1. System Installation Requirements
1-17
TI 32P01J10-01EN
Cabling
Observe the following when cabling the power unit to the ProSafe-RS system equipment:
• Protect signal cables from induced noise.
• Protect signal cables from induction from high-voltage power lines.
• Separate the ProSafe-RS system power supply from other equipment power supplies.
Use a separate power distribution board.
• Provide a dedicated breaker for each power supply.
• Install breakers and devices in the same room.
• Label the breakers with the name of the connected equipment.
• Install the breakers where they can be easily operated.
• The breaker, must not interrupt connection by wiring to protective grounding system.
• As far as possible install power supply cables and high-voltage power lines in metallic
conduits.
• Use shielded cables if metallic conduits cannot be provided.
Mar. 15, 2018-00