3. Cabling
3-4
TI 32P01J10-01EN
Cable Terminals
Use the specified solderless terminals and sleeves for pressure clamp terminal on the end of
terminal-connected cables, providing low contact resistance, high durability, and low aging.
S
olderless Lug
CAUTION
• Be sure to use solderless terminals with insulating sheath.
• Use solderless terminals and crimp tools from the same manufacturer.
• Use appropriate crimp tools meeting the cable size.
F030101.ai
Figure Solderless Terminal with Insulating Sheath
S
leeve for pressure clamp terminal and spring clamp terminal
When connecting the process I/O signal to the pressure clamp terminal of the I/O module, strip
the cable coating (without a sleeve) or attach a sleeve to the cable.
Signal cable
Signal cable
Without sleeve
With sleeve
Sleeve with isolation
cover
Sleeve without isolation
cover
F030102.ai
Figure Sleeve for Pressure Clamp Terminal and spring clamp terminal
CAUTION
• Use a sleeve for pressure clamp terminal and a clamp tool from the same manufacturer.
• Use a sleeve for pressure clamp terminal and a clamp tool which suit the cable size.
• Use a sleeve which meet the DIN 46228 standards.
Bending radius of the cable
When connecting a cable to a system instrument, ensure to secure the minimum bending radius
of the cable.
The minimum bending radius is either the value shown in the cable manufacturer’s specifications
or six-fold of the cable conductor diameter, whichever is bigger should be applied.