7.  TROUBLESHOOTING

If the devices can not communicate each other, perform the 

following checks.

□  All devices related to the communication are turned on.

□  The wiring is correct.

□  The VJ series with Output-2 other than communication is not 

connected.

□  The number of connected devices and connecting distance 

are within the use range.

□  The communication conditions of RS-485 connection device 

are as follows.

□  Protocol: Modbus/RTU

□  Baud rate: 9600 bps

□  Data length: 8 bits

□  Stop bit: 1 bit

□  The Unit ID specified for sending by a host device and the Unit 

ID of the connected RS-485 connection device are consistent.

□  The parity is consistent between VJET and RS-485 connection 

device.

□  The same Unit ID is not set for the devices connected to the 

same communication line.

□  The port number is correct.

□  The IP address is not changed from the factory default.

8.  SAFETY AND EMC STANDARDS

The following will be acquired.

Safety:

CAN/CSA-C22.2 No.61010-1 (CSA)

UL61010-1 (UL)

Overvoltage category: I

Pollution degree: 2

Measurement category: O (other)

Rated power voltage:  24 V DC 1.8 W

Rated transient overvoltage: 1500 V (*)

* This is a reference safety standard value for the 

measurement Category O. This value is not necessarily 

a guarantee of instrument performance.

 CAUTION

This instrument is for Measurement Category O 

(other). Do not use it for measurements in locations 

falling under Measurement Categories II, III, and IV.

    

Internal Wiring

Outlet

Entrance 

Cable

III

T

O

II

IV

Measurement 

category

Description

Remarks

O

(other) For measurements 

performed on circuits not 

directly connected to MAINS.

II

CAT.II For measurements 

performed on circuits directly 

connected to the low-voltage 

installation.

Appliances, 

portable 

equipments, 

etc.

III

CAT.III For measurements 

performed in the building 

installation.

Distribution 

board, circuit 

breaker, etc.

IV

CAT.IV For measurements 

performed at the source of 

the low-voltage installation.

Overhead 

wire, cable 

systems, etc.

EMC standards:

• RCM: 

EN 55011 Class A, Group 1

• KC:

Electromagnetic wave interference prevention standard, 

electromagnetic wave protection standard

 CAUTION

Caution to comply with EMC standards: When 

operating this instrument by external power supply, 

use an independent power unit conforming to the 

respective standards. Be sure to use the lightning 

arrester to comply EMC standards.