4. Configuration Setup
4-11
TI 30A10A30-01E
4.3.6
Port Disable for unused port (shutdown)
To disable particular ports such as unused ports, use “shutdown” command in “Interface Config”
mode. The following example shows the commands for disabling port 5.
F040306.ai
(Hirschmann Railswitch) >enable
(Hirschmann Railswitch) #configure
(Hirschmann Railswitch) (Config)#interface 1/5
(Hirschmann Railswitch) (Interface 1/5)#shutdown
Figure Example of “shutdown” command display
To reactivate the disabled port, use “no shutdown” command in “Interface Config” mode.
F040307.ai
(Hirschmann Railswitch) (Interface 1/5)#no shutdown
Figure Example of “no shutdown” command display
To confirm the port status, see section 4.3.3
4.3.7
Set management IP address (network parms)
To assign a management IP address for the Recommended Switch, use “network parms”
command which is available in “Privileged Exec” mode. Network Management System (NMS) is
a typical application required for this configuration.
An IP address for Vnet/IP open communication is available for the management IP address.
Assign a unique IP address to each Recommended Switch in order to prevent IP address
conflicts.
The following example shows the command to set the management IP address to
192.168.1.130/24.
F040308.ai
(Hirschmann Railswitch) #network parms 192.168.1.130 255.255.255.0
Figure Example of “Network parms” command execution
To confirm the assigned management IP address, see section 4.3.2.
Sep. 19, 2014-00