![YOKOGAWA GRVSW-660FA Technical Information Download Page 30](http://html1.mh-extra.com/html/yokogawa/grvsw-660fa/grvsw-660fa_technical-information_3504035030.webp)
2. Hardware Specifications
2-16
TI 30A10A30-01E
2.5.2
Wiring to Terminal Block
Sleeve attachment for cables
For safe wiring, make sure to use a sleeve for a cable connected to the terminal block for Power
Input or FAULT Output.
Assemble the edge of the cable into the sleeve.
Use appropriate sleeves for applicable cables.
F020401.ai
Length of exposed wire
Core wire
cable
d2
d1
L2
L1
Sleeve with insulation cover
Figure Cable assembly with sleeve
Table Sleeve for Applicable Cables
Cable Thickness
Length of
exposed
wire (mm)
Sleeve dimensions (mm)
Weidmuller
Model
Number
L1
L2
d1
d2
Conductor cross-section
AWG
0.5 mm
2
20
8
12
6
1.0
2.6
H0.5/12
0.75 mm
2
18
8
12
6
1.2
2.8
H0.75/12
1.0 mm
2
17
8
12
6
1.4
3.0
H1.0/12
1.25 to 1.5 mm
2
16
10
14
8
1.7
3.5
H1.5/14
IMPORTANT
• Use the same manufacturer for sleeves and tools.
• Use sleeve tools that match the wire thickness.
• Cut the top of core wire if it extends from the metal tube of the sleeve.