<Toc> <Ind>
<4. Module Access >
4-17
IM 34M6H54-01E
•
Bit number 3: Setting use of input filter
Select whether to use the input filter. The input filter constant setting is common to all
channels.
0: Do not use input filter.
1: Use input filter.
●
Output function
The output function can be set by selecting the output using bits 0 to 9 of the data position
number corresponding to each channel and then setting the output-input interconnections
using bits 12 to 14.
Bit number
TC040206_02.EPS
Output
channel
Data position
number
1
4
2
8
3
12
4
16
15
0
0
0
0
14
0
0
0
1
13
0
0
1
0
12
0
1
0
0
11
0
0
0
0
10
0
0
0
0
9
0
0
0
0
8
0
0
0
0
7
0
0
0
0
6
0
0
0
0
5
0
0
0
0
4
0
0
0
0
3
0
0
0
0
2
0
0
0
0
1
0
0
0
0
0
0
0
0
0
The initial values are defined as follows:
Data position number 4 is set to $0000
“Counter value of input channel 1 = preset value 1 of input channel 1” latched output
Data position number 8 is set to $1000
“Counter value of input channel 2 = preset value 1 of input channel 2” latched output
Data position number 12 is set to $2000
“Counter value of input channel 3 = preset value 1 of input channel 3” latched output
Data position number 16 is set to $4000
“Counter value of input channel 4 = preset value 1 of input channel 4” latched output
•
Output selection
This selects the output type for the comparison results of the counter value with either
preset value 1 or 2, or outputs the counter operating status.
Bit number
Output selection and type
TC040206_03.EPS
9
0
0
0
0
0
0
0
0
0
0
1
8
0
0
0
0
0
0
0
0
0
1
*
7
0
0
0
0
0
0
0
0
1
*
*
6
0
0
0
0
0
0
0
1
*
*
*
5
0
0
0
0
0
0
1
*
*
*
*
4
0
0
0
0
0
1
*
*
*
*
*
3
0
0
0
0
1
*
*
*
*
*
*
2
0
0
0
1
*
*
*
*
*
*
*
1
0
0
1
*
*
*
*
*
*
*
*
0
0
1
*
*
*
*
*
*
*
*
*
Counter value = preset value 1, latched type
Counter value < preset value 1, state type
Counter value
≥
preset value 1, state type
Counter value = preset value 2, latched type
Counter value < preset value 2, state type
Counter value
≥
preset value 2, state type
Preset value 1
≤
counter value < preset value 2, state type
Counter value returns to 0, latched type
Counter operating status (on when stopped), state type
Normally off
Normally on
* Indicates bit position which can be either 0 or 1.
1st Edition : Feb.01,1999-00
Summary of Contents for F3XS04-3N
Page 2: ...Blank Page ...
Page 8: ...Blank Page ...
Page 10: ...Blank Page ...
Page 56: ...Blank Page ...
Page 66: ...Blank Page ...