<Toc> <Ind>
<4. Module Access >
4-7
IM 34M6H54-01E
•
Bit number 2: Stop setting of counter operation
Select the counter operation when the counter values exceeds the ring up-counter
maximum value and returns to 0.
0: When returned to 0, counter operation continues.
1: When returned to 0, counter operation stops.
•
Bit number 3: Setting use of input filter
Select whether to use the input filter. The input filter constant setting is common to all
channels.
0: Do not use input filter.
1: Use input filter.
●
Output function
The output function can be set by selecting the output using bits 0 to 9 of the data position
number corresponding to each channel and then setting the output-input interconnections
using bits 12 to 14.
Bit number
TC040103_02.EPS
Output
channel
Data position
number
1
20
2
24
3
28
4
32
15
0
0
0
0
14
0
0
0
1
13
0
0
1
0
12
0
1
0
0
11
0
0
0
0
10
0
0
0
0
9
0
0
0
0
8
0
0
0
0
7
0
0
0
0
6
0
0
0
0
5
0
0
0
0
4
0
0
0
0
3
0
0
0
0
2
0
0
0
0
1
0
0
0
0
0
0
0
0
0
The initial values are defined as follows:
Data position number 20 is set to $0000
“Counter value of input channel 1 = preset value 1 of input channel 1” latched output
Data position number 24 is set to $1000
“Counter value of input channel 2 = preset value 1 of input channel 2” latched output
Data position number 28 is set to $2000
“Counter value of input channel 3 = preset value 1 of input channel 3” latched output
Data position number 32 is set to $4000
“Counter value of input channel 4 = preset value 1 of input channel 4” latched output
1st Edition : Feb.01,1999-00