3-4
<Toc> <Ind>
<3. Attaching and Wiring Modules >
IM 34M6H54-01E
(2)
Do not reverse the output connections. If an inductive load is connected, connect a
diode in parallel with the load as indicated in Figure 3.5. Connect the diode so that its
cathode will be connected to the positive line of the power supply.
F3XS04-
u
N
OUT –
+
–
OUT +
L
12/24 V DC
OUT –
+
–
OUT +
Diode
L
Transistor
output
Diode
F0305.EPS
Reverse voltage over 10 times the circuit voltage and
forward current over 2 times the load current
Figure 3.5 Connecting Output Terminals
1st Edition : Feb.01,1999-00