9-7
IM 34M6H33-01E
1st Edition : July 1.2004-00
-------------------------------------
Select value to change
-------------------------------------
1 - Change Parameter
2 - Change NV Parameter
3 - Change NV I/O
4 - Change NV ID
5 - Change NV Ext ID1
6 - Change NV Ext ID2
7 - Change Node address
-------------------------------------
Values for node number: 0
I/O 0 NV I/O 0
ID A NV ID 0
ID1 0 NV ID1 0
ID2 0 NV ID2 0
Param 0 NV Param 0
>7<ENTER>
-------------------------------------
Change node address
-------------------------------------
New node address
Back - Esc
-------------------------------------
Old node address: 0
>New address<ENTER>
Select “7 – Change Node address”.
Enter the address number for the change and
press <Enter>.
Save Configuration
This function saves the slave configuration detected when the module is put into
Configuration mode into non-volatile memory.
The saved configuration replaces the current list of projected slaves.
-------------------------------------
AnyBus M ASI Main Menu
-------------------------------------
1 - View scan-lists
2 - View all nodes
3 - View all detected nodes
4 - View single node
5 - Toggle Protected/Configuration
6 - Toggle online/offline
7 - Toggle auto addr. ON/OFF
8 - Save configuration
-------------------------------------
ASi master status:
Offline phase active: False
Power fail: False
Normal operation: True
Slave 0 exist: False
Config mismatch: True
Mode: Configuration
Autoprogramming: Not possible
Bus status: Online
EEPROM status: Ok
Auto addressing: Enabled
>8<ENTER>
-------------------------------------
AnyBus M ASI Save configuration
-------------------------------------
Enter to save configuration
-------------------------------------
<ENTER>
Select “8 – Save configuration”
from the main menu.
Press <ENTER>.
Before saving the configuration, check the configuration by selecting “1 – View scan-
lists” from the main menu.
You can also save the detected configuration by turning the MODE switch on the
module front panel to the SET position for more than 3 seconds.
Summary of Contents for F3LA01-0N
Page 2: ......
Page 26: ...Blank Page...
Page 38: ...Blank Page...
Page 44: ...Blank Page...
Page 54: ...Blank Page...
Page 62: ...Blank Page...
Page 64: ...Blank Page...
Page 70: ...Blank Page...
Page 72: ...Blank Page...
Page 74: ...Index 2 IM 34M6H33 01E 1st Edition July 1 2004 00 Blank Page...
Page 76: ...Blank Page...