9-6
IM 34M6H33-01E
1st Edition : July 1.2004-00
9.3 Setup
Function
Slave address setup and configuration registration can be performed via the monitor
port. Connect the monitor port of the module to the serial port of a PC using an RS-232C
cross cable.
Slave Address Setup
You can perform slave address setup without using an addressing device, but you can
only proceed with one slave at a time by connecting one blank slave (slave with address
0), and changing its address from 0 to the required address.
-------------------------------------
AnyBus M ASI Main Menu
-------------------------------------
1 - View scan-lists
2 - View all nodes
3 - View all detected nodes
4 - View single node
5 - Toggle Protected/Configuration
6 - Toggle online/offline
7 - Toggle auto addr. ON/OFF
8 - Save configuration
-------------------------------------
ASi master status:
Offline phase active: False
Power fail
False
Normal operation: True
Slave 0 exist: False
Config mismatch: True
Mode: Configuration
Autoprogramming:
Not possible
Bus status:
Ok
Auto addressing:
Enabled
>4<ENTER>
-------------------------------------
AnyBus M ASI View single node
-------------------------------------
Select node
-------------------------------------
0<ENTER>
Select “4 – View single node”
from the main menu.
Enter 0 and press <Enter>.
CAUTION
- You cannot connect two or more blank slaves concurrently.
- Always perform slave address modification in Configuration mode. When the module is
in Protected mode with automatic address assignment function enabled, setting to
address 0 is not allowed.
Summary of Contents for F3LA01-0N
Page 2: ......
Page 26: ...Blank Page...
Page 38: ...Blank Page...
Page 44: ...Blank Page...
Page 54: ...Blank Page...
Page 62: ...Blank Page...
Page 64: ...Blank Page...
Page 70: ...Blank Page...
Page 72: ...Blank Page...
Page 74: ...Index 2 IM 34M6H33 01E 1st Edition July 1 2004 00 Blank Page...
Page 76: ...Blank Page...