9-11
IM DR231-01E
Event/Action Function and Other Functions
9
9.1 Setting Event/Action Functions
• MATH (available if the instrument is equipped with the MATH function or floppy disk drive)
• START: Starts computation.
• STOP: Stops computation.
• RESET: Resets computation channel data at the end of completion of the first computation
in case an event takes place.
• CLEAR: Resets computation channel data immediately in case an event takes place.
• RST_G01 to RESET_G07: Resets the computing channel data registered in the specified
group number to 0. This is invalid for measuring channels. The timing for resetting the data
is as follows.
Reset here
Not reset
Computed value
Start computing
Event
• If MATH is selected as a level action, computation will be carried out while an event is
present. Computation will stop when the event is cleared.
• When the level action is set, the start/stop/clear & start computation using using the M.
FUNC key are disable.
• The edge and level actions cannot be set simultaneously. For the level action, only one
action is available.
• MEMRY (available with the DR130-1/DR231-1/DR241-1 equipped with the floppy disk drive)
• DATA_WR: saves one data item to the specified data length each time an event occurs.
• WR_TRIG: saves measured/computed data on the built-in RAM disk.
• RD_TRIG: reads measured/computed data from the built-in RAM disk.
• LD_TRG1 to 3: reads setup data from the built-in RAM disk.
• FLOPY (available only when provided with the "/M1" option or a floppy disk drive):
• LD_TRG1 to 3: reads setup data from the floppy disk.
• FLAG (only for /M1 optional model)
• F01 to 16: Set the flag number (F01 to F16) to 1. F01 to F16 are normally 0. Flags can be
placed in computing equations to hold the computed result using a certain event as a trigger,
or reset to 0.
• REPORT (available if the instrument is equiped with the REPORT function.)
• START (Edge action):
Starts making up a report.
• STOP (Edge action):
Stops making up a report.
• REPORT (Level action): Starts/stops making up a report.
Note
• If, in the SETUP mode, the report function is set to OFF for all data items, you cannot select the action
item REPORT.
Summary of Contents for DR231
Page 12: ...10 IM DR231 01E...