6-3
IM DR231-01E
Setting the Recording Conditions
6
6.1 Setting the Recording Mode/Engineering Unit/Recording Channel and Recording Interval
Setting the Recording Interval (TIMER) of the Digital Printout for the Logging and
Analog Trend Mode
• TIMER No.
You can set up to six recording intervals. A recording interval can be set for each channel
individually. Refer to 6.4 on page 6-9 for details.
• TIME MODE
The following two modes can be selected. The default is RELATIVE.
• RELATIVE; the number of days/hours/minutes can be set to any value between 00 days 00
hours 01 minute to 31 days 23 hours and 59 minutes, in one-minute steps. The default
setting is 00 days, 01 hours and 00 minutes.
• ABSOLUTE; the time interval can be selected from the following settings. The default
setting is 1h.
1min, 2min, 3min, 4min, 5min, 6min, 10min, 12min, 15min, 20min, 30min, 1h, 2h, 3h, 4h,
6h, 8h, 12h, and 24h.
The reference time is set by the hour and minutes. The default value is 00 hrs, 00 min.