<10. Parameter Summary>
10-2
IM 01C27F01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
1.
UAPMO
block
(continued)
104
Reset Energy Left
Initialize the remaining battery life (Energy Left) and
reset it as new batteries.
Perform the battery replacement.
0 = Continue (Cancel)
1 = Reset (Initialization)
0 (reading value
is always 0)
W
105
Power Supply
Status
Indicates the predicted battery level and the power
supply method.
0 = external power supply
1 = battery level 75% or more
2 = battery level 25% ~ 75%
3 = battery level 25% or less
R
106
EHType
Available to write note into this parameter.
---
W
107
Power Supply
Voltage
Indicates the measured power supply voltage (V).
---
R
110
Hardware Write
Protect
Allows recognizing the status of the hardware write
protection switch.
(Switch Off, Switch On)
R
111
Radio Silence
Repeats a cycle of a 1-hour pause and 6-minute
search if the instrument cannot join the network after a
time specified in Radio Silence has elapsed.
When 0 is set, the Radio Silence is invalid.
28800
W
112
Simulation Active
Alert
The On/Off or priority for Simulation Active Alert can
be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
113
Soft Update
incomplete Alert
The On/Off or priority for Soft Update incomplete Alert
can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
Not available for EJX.
1. TRUE
2. 15
W
114
Power low Alert
The On/Off or priority for Power low Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
115
Power Critical low
Alert
The On/Off or priority for Power Critical low Alert can
be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
116
Fault prediction
Alert
The On/Off or priority for Fault prediction Alert can be
set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
Not available for EJX.
1. TRUE
2. 15
W
117
Environmental
conditions Alert
The On/Off or priority for Environmental conditions
Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
118
Outside sensor
limits Alert
The On/Off or priority for Outside sensor limits Alert
can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
119
Out of service Alert The On/Off or priority for Out of service Alert can be
set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W