<9. Maintenance>
9-16
IM 01C27F01-01EN
Integral
Indicator
Factory
NAMUR
category
Bit
Diagnostic
Status
Diagnostic Status Detail
Output actions
Pressure
Static
Pressure
Capsule
Temp
Value
Amp
Temp
Value
AL. 10
PRESS
O
Bit 23 Outside sensor
limits
DP_OUTSIDE_LIMIT
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Sensor
Conversion
not Accurate)
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Non Specific)
Normal action Normal action
AL. 11
ST. PRSS
SP_OUTSIDE_LIMIT
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Non Specific)
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Sensor
Conversion
not Accurate)
Normal action Normal action
AL. 12
CAP. TMP
CAPT_OUTSIDE_LIMIT
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Non Specific)
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Non Specific)
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Sensor
Conversion
not Accurate)
Normal action
AL. 13
AMP. TMP
AMPT_OUTSIDE_LIMIT
Normal action Normal action Normal action
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Sensor
Conversion
not Accurate)
AL. 53
P. ADJ
C
Bit 25
Installation,
calibration
problem
DP_TRIM_SPAN_
OUTSIDE
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Range Limits
Exceeded)
Normal action Normal action Normal action
AL. 53
P. ADJ
DP_TRIM_ZERO_
OUTSIDE
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Range Limits
Exceeded)
Normal action Normal action Normal action
AL. 55
SP. ADJ
SP_TRIM_SPAN_
OUTSIDE
Normal action
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Range Limits
Exceeded)
Normal action Normal action
AL. 55
SP.ADJ
SP_TRIM_ZERO_
OUTSIDE
Normal action
Output value
(calculated in
a normal way)
Output status
(UNCERTAIN:
Range Limits
Exceeded)
Normal action Normal action
AL. 79
OV. DISP
LCD_OUTSIDE_LIMIT
Normal action Normal action Normal action Normal action