52
IM CW500-02EN
Estimated value (DEM
Guess
)
Display digits
6 digits
Displayed unit
m, k, M, G, T (match with DEM
Target
)
Display range
0.00000 mW (VA) to 99999.9 TW (VA)
*
Match the decimal place with DEM
Target
.
*
OL is displayed when the display range is exceeded.
Equation
DEM
Guess
=
ΣDEM × measurement interval time/time from measurement
start to present
Current value, demand measurement (ΣDEM)
Display digits
6 digits, unit: m, k, M, G, T
*
Match with DEM
Target
Displayed unit
m, k, M, G, T
*
Match with DEM
Target
Display range
0.00000 mW (VA) to 99999.9 TW (VA)
*
Match the decimal place with DEM
Target
.
*
OL is displayed when the display range is exceeded.
Equation
ΣDEM
=
(Integrated value of "+WPsum (+WSsum)"
from measurement start to present) ×
1 hour
Measurement interval time
Load factor
Display digits
6 digits
Display range
0.00 to 9999.99%
*
OL is displayed when the display range is exceeded.
Equation
ΣDEM / DEM
Terget
Estimation
Display digits
6 digits
Display range
0.00 to 9999.99%
*
OL is displayed when the display range is exceeded.
Equation
DEM
Guess
/ DEM
Terget
Specifications