background image

Summary of Contents for ASGW

Page 1: ...User s Manual ASGW Analyzer Server Gateway IM11B06E01 01E IM 11B06E01 01E 2006 03 Primary edition...

Page 2: ...3 Alarm information 3 1 3 4 Modbus interface table 3 2 4 Engineering 4 1 4 1 Installation 4 1 4 1 1 Preparation 4 1 4 1 2 Initial setting 4 1 4 2 Data mapping 4 3 4 3 Loading a mapping file 4 3 4 4 Se...

Page 3: ...accessed between multiple analyzers and DCS This system provides efficient engineering and communication performance ASGW has two type interfaces Modbus TCP Ethernet one port and Mobus RTU serial Mod...

Page 4: ......

Page 5: ...Name Item Remarks NFJT100 S0x FCJ Note x is the G3 option 2 2 Software configuration ASGW requires the license and software shown below License Code Item Remarks NT711AJ LM03E FCN FCJ basic software...

Page 6: ......

Page 7: ...31 sets Function Available address for mapping Available points GC1000 address area Coil 01001 09000 8000 Coil Input relay Input relay 11001 19000 8000 Input relay Holding register 41001 49000 8000 In...

Page 8: ...0x05 BIT 1 bit Write single register 6 0x06 WORD 1 word Loopback test 8 0x08 WORD 1 word Force multiple coils 15 0x0F BIT 800 bits Write multiple registers 16 0x10 WORD 100 words Read devise ID 43 0x2...

Page 9: ...g for ASIU is invalid Value turns to 0 after writing Mapping area 01001 09000 Setting the address of coil and input relay of GC1000MkII ASIU ASGW only reads the input relay on GC1000MkII ASIU ASGW onl...

Page 10: ...relay of GC1000MkII ASIU ASGW reads the addressed data on GC1000MkII ASIU Holding register 40001 49999 Data Address Description Time setting value 40001 40002 40003 40004 Setting the clock time Refer...

Page 11: ...ncertain DCS can write on coil or holding register of ASGW that is not defined however ASGW does not write it on analyzers and the written data is kept on ASGW until turning off Retry to writing When...

Page 12: ......

Page 13: ...license file from the STARDOM license publishing web site Setting the system card Set the system compact flash card combined with FCJ on PC Click the following batch file Uncompressed folder INSTALL_A...

Page 14: ...r 3 To enable Java 4 Setting the network Ethenet of ASGW has dual or single type and dual type has duplex and separated mode Select the type and mode for the system Reboot the ASGW After starting ASGW...

Page 15: ...e After the installation of ASGW turn on the power and connect the ASGW to PC with Ethernet cable Open the web browser on PC and input the address of ASGW as http IP address of ASGW When the homepage...

Page 16: ...on communication speed Unit is ms millisecond and range is 10 to 5000 Definition of GC1000MkII ASIU This is the setting of analyzer ID The number of analyzer units that is connected to one ASGW is 31...

Page 17: ...nosis information After re starting the ASGW Open the web browser When Mapping Error is clicked the diagnosis information window appears The contents are as follows a Out of range addressing b Duplica...

Page 18: ......

Page 19: ...the IP address setting mode One is use of web browser on PC the other is use of switches on CPU module Select one depending on the location of ASIU ASGW During the IP address setting mode LEDs on CPU...

Page 20: ...5 3 IM 12Y04D01 01 Password YOKOGAWA ii Click the Maintenance Menu...

Page 21: ...5 Additiona Information IM 12Y04D01 01 5 2 iii Click the Reboot iii Select the Reboot IP Address Setting Mode and press OK ASIU ASGW restarts on IP address setting mode...

Page 22: ...IM 12Y04D01 01 3 Setting IP address Start the resource configurator software on PC and wait for a message A new controller is connected When the message appears select the Setting IP Address on File m...

Page 23: ...ASIU ASGW this operation is required ASIU has one and ASGW has two communication ports and all initial setting data are as follows After ASIU ASGW mode changes to maintenance mode the communication p...

Page 24: ...5 3 IM 12Y04D01 01...

Page 25: ...5 Additiona Information IM 12Y04D01 01 5 2...