3-4
IM
11B06E01-01
Input relay(10001-19999)
Data Address
Description
In operation
10xxx
Operation condition makes the
value to “1”.
“xxx” is Stn ID
“xxx” (=001 – 254)
Communication Failure
10yyy
Communication error makes
the value into “1”.
“yyy” is 300+Stn ID
“yyy” (=301 – 554)
Write error
10zzz
Write error makes the value
into “1”, and recovery in next
access makes it into “0”.
“zzz” is 600+Stn ID
“zzz” (=601-854)
Mapping area
11001-19000
Setting the address of input
relay of GC1000MkII/ASIU.
ASGW reads the addressed
data on GC1000MkII/ASIU.
Holding register(40001-49999)
Data Address
Description
Time setting value
40001
40002
40003
40004
Setting the clock time.
Refer to General Specification
of GC1000 communication
function
(GS 11B3G1-02E) for data
format.
The data are kept after writing
on GC1000MkII.
Mapping area
41001-49000
Setting the address of input
register or holding register of
GC1000MkII/ASIU.
ASGW only reads the input
register on
GC1000MkII/ASIU.
ASGW only writes the holding
registor on GC1000MkII.
Available register of
GC1000MkII
44101-47199: range change
The other address area is
ignored.