BRIEF UNIT INFORMA
TION
BRIEF UNIT INFORMA
TION
P14 OF 34
P13 OF 34
USER NOTES AND SERVICE LOG
OUTDOOR UNIT WORKING TEMPERATURE RANGE
Maximum cooling
Minimum cooling
Maximum heating
Minimum heating
o
Outdoor side DB( F)
115(T1)
20
75
5
SPECIFICATION
Outdoor Unit Models
WMMS-21CH-V2B(59)(2) (1 to 2)
WMMS-30CH-V2B(59)(2) (1 to 2)
WMMS-24CH-V2B(59)(2) (1 to 3)
WMMS-36CH-V2B(59)(2) (1 to 3)
WMMS-48CH-V2B(59)(2) (1 to 4)
WMMS-42CH-V2B(59)(2) (1 to 4)
Power Supply
208-230/1/60
Cooling Capacity*
(Btu/h)
Max. Allowed IDU Cap. Total
30,000
36,000
48,000
57,000
Rated
18,000
24,000
28,000
30,000
Min.
7,200
10,000
10,000
10,000
Total Power Input in
Cooling Mode* (W)
Max.
2300
3300
4500
4500
Rated
1550
2250
2600
2600
Min.
650
800
900
1000
SEER
HSPF
16.0
8.2
16.0
8.2
16.0
8.2
16.0
8.2
Heating Capacity*
(Btu/h)
32,000
38,000
50,000
59,000
Rated
19,000
29,500
31,000
33,000
Min.
6,500
9,000
9,000
9,000
Total Power Input in
Heating Mode*
Max.
2400
3000
3500
3500
Rated
1750
2500
2920
2920
Min.
650
800
900
1000
WMMS-60CH-V2B(59)(2) (1 to 5)
72,000
42,000
12,000
5100
3950
1200
16.0
8.2
74,000
46,000
10,000
4800
4400
1200
Compressor Manufacturer/trademark
Liquid Valve Size
2 x 1/4"
3 x 1/4"
4 x 1/4"
4 x 1/4"
Gas Valve Size
2 x 3/8"
3 x 3/8"
4 x 3/8"
4 x 3/8"
Sanyo / Mitsubishi / Others
Sanyo / Mitsubishi / Others
Sanyo / Mitsubishi / Others
Sanyo / Mitsubishi / Others
Throttling Method
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Starting Method
Transducer starting
Transducer starting
Transducer starting
Transducer starting
Recommended Working Ambient Temp Ranges (F)
AC: 20 to 115 HP: 5 to 75
AC: 20 to 115 HP: 5 to 75
AC: 20 to 115 HP: 5 to 75
AC: 20 to 115 HP: 5 to 75
Condenser
Aluminum fin-copper tube
Aluminum fin-copper tube
Aluminum fin-copper tube
Aluminum fin-copper tube
Output of Fan Motor (W)
60
60
60
60
Fan Motor RLA (A)
0.65
0.65
0.65
0.65
Fan Motor Capacitor (uF)
3
3.5
3.5
3.5
Air Flow Rate of Outdoor Unit
/
/
/
/
Fan Type-Piece
Axial fan 1
Axial fan 1
Axial fan 1
Axial fan 1
Fan Diameter (Inches)
18.1
18.1
18.1
18.1
Defrosting Method
Auto Defrost
Auto Defrost
Auto Defrost
Auto Defrost
Climate Type
T1
T1
T1
T1
Isolation
I
I
I
I
Moisture Protection
IP24
IP24
IP24
IP24
Max. Operating Pressure at High Side (PSI)
550
Max. Operating Pressure at Low Side (PSI)
175
Sound Pressure Level dB (A) (H/L)
56/54
56/54
56/54
56/54
Sound Power Level dB (A) (H/L)
66/64
66/64
66/64
66/64
Dimensions of Outdoor Unit (W x H x D) (Inches)
33.3 x 27.0 x 11.8
37.4 X 27.5 X 15.5
37.2 X 27.6 X 15.75
37.4 X 27.5 X 15.5
Dimensions of Package (W x H x D) (Inches)
39.1 x 29.5 x 16.9
40.6 X 29.5 X 16.5
40.5 X 29.5 X 18.0
40.6 X 29.5 X 16.5
Net Weight /Gross Weight (LBs)
115 / 126
150 / 161
165 / 176
165 / 176
Refrigerant /Factory Pre-Charge for 25' (LBs)
R410A / 2.97
R410A / 4.84
R410A / 4.84
R410A / 4.84
Loading
Quantity
20' Container
87
80
80
80
40' Container
183
170
170
170
40' High Cube Container
183
170
170
170
550
550
550
175
175
175
30
30
30/40
40
L.R.A. (A)
27
45
45
45
Compressor RLA (A)
8.4
9.7
9.7
10
Compressor Power Input (W)
1245
2200
Fuse or Circuit Breaker (HVAC Type)
MCA (A)
15
20
20/30
30
Compressor Oil
/ FV50S /
/ FV50S /
/ FV50S /
/ FV50S /
2200
2200
4 x 1/4" + 3/8"
2 x 3/8" + 2 x 1/2" + 5/8"
Sanyo / Mitsubishi / Others
Electronic Expansion Valve
Transducer starting
AC: 20 to 115 HP: 5 to 75
Aluminum fin-copper tube
140
1.1
6
/
Axial fan 1
22.5
Auto Defrost
T1
I
IP24
56/54
66/64
42.25 X 43.5 X 17.5
46.0 X 48.6 X 19.4
225 / 248
R410A / 10.6
50
100
100
550
175
50
55
13
50
/ FV50S /
3000
Max. Allowed IDU Cap. Total
YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !
YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !
SAMPLE SIZE COMBINATIONS AND PERFORMANCE DATA
1) The DC inverter outdoor unit may work with many different combinations of styles (wall, ceiling, ceiling/floor, concealed, etc.) and sizes of indoor units.
2) In real world, there might be small percentage of applications where all indoor units will be working at peak demand of cooling or heating needs. One room
could be at peak demand, others may not. This way, the outdoor unit doesn't need to work at peak speed/load all the time.
3) Not all pairs of refrigerant valves need to be connected at initial installation. But, there is minimum amount of indoor units shall be connected (refer to the spec.
sheet for details).
If only few of indoor units are installed initially, other indoor units can still be installed in the future whenever ready (need to vacuum and adjust refrigerant
charge accordingly).
4) These outdoor unit can only drive all indoor units for one thermal mode at one time. Shall not run cooling in one indoor unit, and heating in another one. In
case of mode conflict or clash, correct the thermal mode which is different from others, or shut off power and select one thermal mode for all indoor units.
Indoor Unit
Combinations
Total
Capacity
Room A
Room B
Room C
Room D
Capacity Rating-Btu/h
(Min.
Max.)
Input Power Rating-Watts
(Min.
Max.)
WMMS-2AM21-V2B(59)(2) / WMMS-2AM30-V2B(59)(2) Cooling Performance Nominal Data
9K
9K
10880
10880 (9180~12240)
1050 (1000~1300)
12K
12K
11900
11900 (9180~14960)
1050 (1000~1500)
18K
18K
17000
17000 11220~22780)
(
1400 (1000~2600)
9+9K
18K
8500
8500
17000 11220~22780)
(
1400 (1000~2600)
9+12K
21K
8500
11900
20400 11220~26520)
(
1800 (1000~3300)
12+12K
24K
11900
11900
23800 11220~27880)
(
2300 (1000~3800)
9+18K
27K
8840
15300
24140 11220~32300)
(
2200 (1000~4600)
12+18K
30K
11900
12240
24140 11220~32300)
(
2200 (1000~4600)
9+9+9K
27K
8075
8075
8075
24140 11220~32300)
(
2200 (1000~4600)
9+9+12K
30K
7140
7140
9860
24140 11220~32300)
(
2200 (1000~4600)
9+12+12K
33K
6460
8840
8840
24140 11220~32640)
(
2200 (1000~4650)
12+12+12K
36K
8075
8075
8075
24140 11220~32640)
(
2200 (1000~4650)
9+9+18K
36K
7480
7480
9180
24140 11220~32640)
(
2200 (1000~4650)
9+12+18K
39K
7140
7820
9180
24140 11220~32640)
(
2200 (1000~4650)
12+12+18K
42K
7820
7820
8500
24140 11220~32640)
(
2200 (1000~4650)
WMMS-3AM24-V2B(59)(2) / WMMS-3AM36-V2B(59)(2) Cooling Performance Nominal Data
9+9K
18K
8500
8500
17000 11220~22780)
(
1400 (1000~2600)
9+12K
21K
8500
11900
20400 11220~26520)
(
1800 (1000~3300)
12+12K
24K
11900
11900
23800 11220~27880)
(
2300 (1000~3800)
9+18K
27K
8840
15300
24140 11220~32300)
(
2200 (1000~4600)
12+18K
30K
11900
12240
24140 11220~32300)
(
2200 (1000~4600)
9+9K
18K
8500
8500
1400 (1000~2600)
9+12K
21K
8500
11900
1800 (1000~3300)
9+9+9K
27K
8044
8044
8044
2200 (1000~4600)
9+9+12K
30K
7140
7140
9860
2200 (1000~4600)
9+12+12K
33K
6460
8840
8840
2200 (1000~4650)
12+12+12K
36K
8044
8044
8044
2200 (1000~4650)
9+9+18K
36K
7480
7480
9180
2200 (1000~4650)
9+12+18K
39K
7140
7820
9180
2200 (1000~4650)
12+12+18K
42K
7820
7820
8500
2200 (1000~4650)
9+9+9+9K
36K
6800
6800
6800
6800
2480 (1000~4650)
9+9+9+12K
39K
1750
1750
1750
2750
2480 (1000~4650)
9+9+12+12K
42K
1500
1500
2500
2500
2480 (1000~4700)
9+12+12+12K
45K
1700
2100
2100
2100
2480 (1000~4700)
WMMS-4AM42-V2B(59)(2) Cooling Performance Nominal Data
Indoor Unit
Combinations
Total
Capacity
Room A
Room B
Room C
Room D
Capacity Rating-Btu/h
(Min.
Max.)
Input Power Rating-Watts
(Min.
Max.)
12+12K
24K
11900
11900
2300 (1000~3800)
9+18K
27K
8840
15300
2200 (1000~4600)
12+18K
30K
11900
12240
10880 (9180~12240)
11900 (9180~14960)
17000 (11220~22780)
17000 (11220~22780)
20400 (11220~26520)
24140 (11220~32300)
24140 (11220~32300)
24140 (11220~32640)
24140 (11220~32640)
24140 (11220~32640)
24140 (11220~32640)
24140 (11220~32640)
27200 (11220~32640)
23800 (11220~27880)
24140 (11220~32300)
24140 (11220~32300)
2200 (1000~4600)
Indoor Unit
Combinations
Total
Capacity
Room A
Room B
Room C
Room D
Capacity Rating-Btu/h
(Min.
Max.)
Input Power Rating-Watts
(Min.
Max.)
9+9K
10880
10880
21760 (8670~27880)
2050 (900~2950)
9+12K
10880
13600
24480 (8670~28900)
2300 (900~3300)
12+12K
13260
13260
26520 (10200~31620)
2400 (900~3500)
9+18K
9860
17000
26860 (10200~31620)
2400 (900~3500)
12+18K
12240
15300
27540 (10540~33660)
2400 (1000~3900)
9+9+9K
9180
9180
9180
27540 (10540~33660)
2400 (1000~4000)
9+9+12K
8500
8500
10540
27540 (10540~33660)
2400 (1000~4000)
9+12+12K
7480
10370
10370
28220 (10540~33660)
2450 (1000~4000)
9+9+18K
7990
7990
11560
27540 (10540~33660)
2400 (1000~4000)
12+12+12K
9690
9690
9690
29070 (10540~33660)
2500 (1000~4000)
9+12+18K
7480
9180
10880
27540 (10540~33660)
2400 (1000~4000)
12+12+18K
8500
8500
10540
27540 (10540~33660)
2400 (1000~4000)
9+9+9+9K
8160
8160
8160
8160
32640 (11220~37400)
2600 (1100~4200)
9+9+9+12K
7480
7480
7480
10200
32640 (11220~37400)
2600 (1100~4200)
9+9+12+12K
7140
7140
9180
9180
32640 (11220~37400)
2600 (1100~4200)
9+12+12+12K
18K
21K
24K
27K
30K
27K
30K
33K
36K
36K
39K
42K
36K
39K
42K
45K
6120
8840
8840
8840
32640 (11220~37400)
2600 (1100~4200)
Indoor Unit
Combinations
Total
Capacity
Room A
Room B
Room C
Room D
Capacity Rating-Btu/h
(Min.
Max.)
Input Power Rating-Watts
(Min.
Max.)
WMMS-4AM42-V2B(59)(2) Heating Performance Nominal Data
Indoor Unit
Combinations
Total
Capacity
Room A
Room B
Room C
Room D
Capacity Rating-Btu/h
(Min.
Max.)
Input Power Rating-Watts
(Min.
Max.)
9K
9K
9860
9860 (6630~15980)
1100 (850~2450)
12K
12K
13260
13260 (6800~17000)
1450 (850~2500)
18K
18K
19720
19720 (8670~27880)
1850 (900~2950)
9+9K
18K
10880
10880
21760 (8670~29240)
2050 (900~2950)
9+12K
21K
10880
13600
24480 (8670~30600)
2300 (900~3300)
12+12K
24K
13260
13260
26520 (10200~32640)
2400 (900~3500)
9+18K
27K
12240
17000
26860 (10200~31620)
2400 (900~3500)
12+18K
30K
12240
15300
27540 (10540~33660)
9+9+9K
27K
9632
9632
9632
28900 (10540~37400)
9+9+12K
30K
9010
9010
10880
28900 (10540~37400)
9+12+12K
33K
7820
10880
10880
29580 (10540~37400)
2400 (1000~3900)
2350 (1000~4000)
2350 (1000~4000)
2400 (1000~4000)
9+9+18K
36K
7990
7990
13600
29580 (10540~37400)
12+12+12K
36K
9860
9860
9860
29580 (10540~37400)
9+12+18K
39K
7480
9180
12920
29580 (10540~37400)
12+12+18K
42K
8500
8500
12580
29580 (10540~37400)
2600 (900~3800)
2600 (900~3800)
2600 (900~3800)
2600 (900~3800)
9+9K
18K
10880
10880
21760 (8670~29240)
2050 (900~2950)
9+12K
21K
10880
13600
24480 (8670~30600)
2300 (900~3300)
12+12K
24K
13260
13260
26520 (10200~32640)
2400 (900~3500)
9+18K
27K
12240
17000
26860 (10200~31620)
2400 (900~3500)
12+18K
30K
12240
15300
27540 (10540~33660)
WMMS-3AM24-V2B(59)(2) / WMMS-3AM36-V2B(59)(2) Heating Performance Nominal Data
WMMS-2AM21-V2B(59)(2) / WMMS-2AM30-V2B(59)(2) Heating Performance Nominal Data
Indoor Unit
Combinations
Total
Capacity
Room A
Room B
Room C
Room D
Capacity Rating-Btu/h
(Min.
Max.)
Input Power Rating-Watts
(Min.
Max.)
RECOMMENDED MATCHING INDOOR AND OUTDOOR UNITS (NOT ALL
POSSIBILITIES BEING LISTED)
1 Indoor Unit
2 Indoor Units
3 Indoor Units
4 Indoor Units
09K
12K
18K
09K+12K
09K+09K
1 Indoor Unit
2 Indoor Units
3 Indoor Units
4 Indoor Units
4 Indoor Units
09K+12K
09K+18K
12K+12K
09K+09K+09K
09K+09K+12K
09K+09K+18K
1 Indoor Unit
2 Indoor Units
3 Indoor Units
Not allowed
Not allowed
09K+09K+12K
09K+12K+12K
09K+09K+09K+09K
09K+09K+09K+12K
09K+09K+12K+12K
12K+12K
09K+18K
09K+12K+18K
09K+09K+24K
12K+12K+18K
09K+12K+12K+12K
12K+12K+12K+12K
09K+09K+09K+18K
12K+18K
1 Indoor Unit
2 Indoor Units
3 Indoor Units
4 Indoor Units
09K+09K+09K
09K+09K+12K
09K+12K+24K
09K+12K+12K
09K+09K+09K+09K
09K+12K+12K+18K
09K+09K+09K+12K
09K+09K+12K+18K
09K+09K+09K+18K
09K+09K+12K+24K
09K+12K+12K+24K
12K+18K
09K+24K
09K+09K+18K
12K+12K+12K
09K+12K+18K
12K+12K+24K
09K+09K+09K+24K
12K+12K+12K+12K
12K+12K+18K
Not allowed
Not allowed
Not allowed
Not allowed
12K+24K
12K+24K
18K+18K
09K+12K+12K
09K+12K+18K
12K+12K+12K
18K+18K
Important Notes:
Indoor Unit Mix and Match Size Possibilities (Samples), to Work with: Outdoor Unit WMMS-21CH-V2B(59)(2) / WMMS-30CH-V2B(59)(2)
Indoor Unit Mix and Match
Size Possibilities (Samples), to Work with: Outdoor Unit WMMS-24CH-V2B(59)(2) / WMMS-36CH-V2B(59)(2)
Indoor Unit Mix and Match
Size Possibilities (Samples), to Work with: Outdoor Unit WMMS-42CH-V2B(59)(2)
Indoor Unit Mix and Match
Size Possibilities (Samples), to Work with: Outdoor Unit WMMS-48CH-V2B(59)(2)
12K+12K
12K+18K
24K
1 Indoor Unit
Not allowed
Indoor Unit Mix and Match Size Possibilities (Samples), to Work with: Outdoor Unit WMMS-60CH-V2B(59)
(2)
2 Indoor Units
5 Indoor Units
09K+09K+09K+12K+12K/18K/24K
09K+12K+12K+12K+12K/18K
09K+09K+12K+12K+18K
09K+12K+12K+18K+18K
12K+12K
18K+18K
18K+24K
12K+18K
12K+24K
24K+24K
3 Indoor Units
09K+09K+09K
09K+09K+18K
12K+12K+12K
09K+09K+12K
12K+12K+18K
12K+12K+24K
09K+12K+12K
09K+12K+18K
09K+12K+24K
4 Indoor Units
09K+09K+09K+12K
09K+09K+12K+18K
09K+09K+12K+24K
09K+09K+09K+09K
09K+12K+12K+18K
09K+12K+12K+24K
09K+09K+09K+18K
12K+12K+12K+12K
12K+12K+12K+24K
09K+09K+09K+09K+12K/18K/24K
09K+09K+12K+12K+12K/18K/24K
12K+12K+12K+12K+12K/18K
09K+09K+12K+18K+18K
12K+12K+12K+18K+18K
18K+24K
18K+18K
24K+24K
18K+24K
9K+9K+9K
9K+9K+18K
12K+12K+12K
09K+12K+24K
09K+09K+12K+18K
* When the rated total capacity of all the indoor units exceeds the rated capacity of outdoor unit, each indoor unit may not output the rated
capacity and one may differ from other, upon other installation/operation factors, it all units are turned on to run compressor simultaneously.
* Must follow pipe length and refrigerant charge adjustment as instructed in below table:
PIPE ADAPTOR
Whenever the outdoor unit gas valve of size 3/8" is to connect with indoor unit gas pipe of 1/2" or 5/8",
one 3/8" - 1/2" or 3/8" - 5/8" adaptor is to be used in between. This reducer is packed separately and
shall be installed at job site.
PIPE ADAPTOR
PIPE FROM
INDOOR UNIT
OUTDOOR UNIT VALVE
OUTDOOR UNIT WORKING TEMPERATURE RANGE