INSTALLATION POSITIONS FOR OUTDOOR UNIT

* To be installed at the position where the air delivered from the unit can reach every comer of the room.
* To avoid being affected by the outdoor air.
* To avoid blockage to the air inlet or outlet of the unit.
* To avoid too much oil smoke or steam.
* To avoid possible generation, inflow, lingering or leakage of flammable gases.
* To avoid high-frequency facilities (such as high frequency arc welders, etc.).
* To avoid the places where acid solutions are frequently used.
* To avoid the places where some special sprayers (sulfides) are frequently used.
* Not to install on top of the musical instruments, TV, computer etc. valuable appliance.
* Not to install a fire alarming device near the air outlet of the unit (during operation, the fire alarm device might 
  be erroneously triggered by the warm air from the unit).

The installation must be done by trained and 
qualified service personnel with reliability 
according to this manual.

Contact service center if you have any 
questions, be for or during or after installation, 
in order  to avoid the malfunction or failure due 
to unprofessional installation.

Picking up and moving the units, you must be 
guided by trained and qualified personal, with 
proper tool.

Ensure that the recommended clearance is left 
around the unit, for proper installation, 
operation and service in the future..

WMMS-42CH-V2B(59)(2) (1 to 4)

WMMS-21CH-V2B(59)(2) (1 to 2)
WMMS-30CH-V2B(59)(2) (1 to 2)

WMMS-48CH-V2B(59)(2) (1 to 4)

WMMS-24CH-V2B(59)(2) (1 to 3)
WMMS-36CH-V2B(59)(2) (1 to 3)

Inch

Model

B

E

Inch

13.5

21.7

13.5

22.75

13.5

22.75

13.5

22.5

INSTALLATION CLEARANCE

WMMS-60CH-V2B(59)(2) (1 to 5)

16.9

24.75

>18"

>18"

Other Brackets

Heavy-Duty PVC Riser

for Ground Mounting

Coated Brackets 

W A ccessories       

Bracket Accessories 

INSTALLATION-OUTDOOR UNIT

INSTALL OUTDOOR UNIT

Strongly suggest to install the outdoor unit above the ground either on platform or brackets as shown below. 

Heat pump unit must be lift up from ground level, since condensate must be drained out of the drain pan of the 
condensing unit; othewise, condensate may be iced and built up to damage the condensing unit.

Suggest to use YMGI-provided brackets and condensate drainage fitting accessories.

(Actual unit/parts or installation may look differently from the illustrated)

PIPING AND WIRING SIZES-UNITS MADE AFTER 09/2012

Unit    

Connection Copper
Pipe Sizes            

Min/Max.Length
+/- Elevation     

Wires from Outdoor
to Each Indoor Unit         

Mini. Wire Size from
Outdoor to Circuit Breaker

HVAC Type
Circuit Breaker

21/30CH

2*(1/4+3/8")

15/75/25/35       

N(1)/2/3/G             

12AWG                    

30AMP

24/36CH

3*(1/4+3/8")

15/75/25/35       

N(1)/2/3/G             

10AWG                    

42CH

48CH

60CH

4*(1/4+3/8")

15/75/25/35       

N(1)/2/3/G             

10AWG                    

4*(1/4+3/8")

2*(1/4+3/8")+2*(1/4+1/2")
+(1/4+5/8")

15/75/25/35       

15/75/25/35       

N(1)/2/3/G             

N(1)/2/3/G             

8AWG                    

8AWG                    

30AMP

40AMP

40AMP

50AMP

Disconnect switch box for outdoor unit

Non-Metalic Power Whip 

for Outdoor Use 

(Field-Supplied, Not Spliced 

and Not Knotted, 

Water-Proof Sealed Tight, 

UL Approved)

Bring in line-voltage power input 
wires from circuit breaker to line-
voltage wire terminal block at outdoor 
unit. Pass through certified wire pipes, 
harnesses and knockouts. Enough 
length shall be left for future service. 
Only copper wire is allowed.

Strictly follow NEC or state or local 
codes to select wires, circuit breaker, 
conduits and to perform installation 
work.

INSTALLATION & PICTURES-WALL MOUNT BRACKET FOR OUTDOOR UNIT(S) 
(PART VARIES UPON MODELS/AVAILABILITY)

* Select a secured location where the outdoor unit will be installed properly.

* Orient the unit rear side (intake grill) towards wall and front side (discharge grill) away from wall.
* For ground installation, use factory-provided riser and accessories. Not to bolt unit feet directly onto ground. 
  Riser or brackets shall be levelled at outdoor unit foot surfaces. Secure unit foot by tightening bolts, nuts and 
  anti-vibration pads.

* For wall mount installation, use factory-provided brackets, anchors and accessories. 

* Remove the wiring diagram cover where also the 
  handle for moving unit is located.

* Follow the wiring diagrams on the unit or the wiring 
  diagram manual that comes with the indoor unit to 
  get familiar with wiring and make sure nothing is 
  made wrong. If there is any discrepancy, always use 
  the one put in the units.

* Connect wires between indoor unit and outdoor 
  unit-power wire from outdoor to Indoor, control wires 
  from Indoor unit to outdoor unit. Pass wire through 
  certified wire pipes, harnesses and knockouts. 
  Enough length shall be left for future service. Only 
  copper wire is allowed.

CONNECT WIRING BETWEEN OUTDOOR UNIT AND INDOOR UNIT 

OUTDOOR WIRING: OUTDOOR-INDOOR UNIT & DISCONNECT SWITCH 
BOX/CIRCUIT BREAKER/FUSE

WIRING OUTDOOR UNIT

* Check the nameplate for rated electrical data. Connect unit to the correct electrical power source.

O

O

* Select power wire of proper type and size. Suggest to use UL approved 105 C/221 F multi-strand copper wire 
  for outdoor use. Refer to the following tables, for proper selection of wire gauge, size and circuit breaker.

WIRING OUTDOOR UNIT

INSTALLATION-OUTDOOR UNIT

Summary of Contents for WMMS-21CH

Page 1: ...NY CHOIR OUTDOOR UNIT CH This product is designed and manufactured free from defects in material and workmanship for normal use and maintenance Installation operation maintenance and service shall fol...

Page 2: ...or your NEW home unit is not checked or used yet is closed whichever comes later by the owner s to Warranty Department YMGI Group POB 1559 O Fallon MO 63366 USA A full copy of Warranty Registration C...

Page 3: ...leakage before and after connecting them 28 Do you list the working details in the invoice and leave a copy to the customer 19 Did you charge the inter connection copper pipes and indoor unit with nit...

Page 4: ...operly can be more expensive than spending the little extra money that hiring the right contractor will cost Protect your investment and warranty eligibility by doing it right the first time THE FOLLO...

Page 5: ...ity to claim freight damage is lost and YMGI will not replace the unit on this basis Contact the distributor or YMGI report the damage by forwarding the marked delivery receipt copy and pictures Only...

Page 6: ...Service Center for Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to the YMGI Group 3 Once the form has been co...

Page 7: ...rag wires too hard or use wire to hang or band or fasten anything Must turn off unit and disconnect electrical power before cleaning or servicing the unit Suggest to put a warning sign at the switch t...

Page 8: ...39K 7140 7820 9180 2200 1000 4650 12 12 18K 42K 7820 7820 8500 2200 1000 4650 9 9 9 9K 36K 6800 6800 6800 6800 2480 1000 4650 9 9 9 12K 39K 1750 1750 1750 2750 2480 1000 4650 9 9 12 12K 42K 1500 1500...

Page 9: ...a flat solid floor When mounting the unit on a wall or the roof make sure the support is firmly secured so that it cannot move in the event of intense vibrations or a strong wind Do not install the o...

Page 10: ...SIZES UNITS MADE AFTER 09 2012 Unit Connection Copper Pipe Sizes Min Max Length Elevation Wires from Outdoor to Each Indoor Unit Mini Wire Size from Outdoor to Circuit Breaker HVAC Type Circuit Break...

Page 11: ...reduce the bending of the piping line as much as possible so as to avoid possible negative impacts upon the performances of the units Make Oil trap if elevation drop difference is more than 25 as illu...

Page 12: ...N 1 2 3 N 1 2 3 D C B A Left Right YMGI Engineered Comfort Products for A Sustainable and Efficient Green World YMGI Engineered Comfort Products for A Sustainable and Efficient Green World ELECTRICAL...

Page 13: ...IRING DIAGRAMS WARNING L BN WH BL YE AC L1 AC N1 AC N3 AC L3 27RD 36RD PR N 26BK 35BK W38 W37 X5 X3 X4 U V W P N W39 AP2 AP3 AP4 PR N AC L1 AC N1 XH 3 20BN 21BU X6 X1 X101 X12 X14 19YEGN E X10 AC L X9...

Page 14: ...h Capacity Size Inch 17 7 21 7 15 4 18 3 320 360 09K 18K 18K 60K Made of stainless steel Model BRKT 0918 ST1 BRKT 1860 ST1 A B LBs Btu h Capacity Size Inch 17 7 21 7 15 4 18 3 320 360 09K 18K 18K 60K...

Page 15: ...sure the unit is ready for trial running check wires and pipes and air intake and discharge and power and thermostat and others necessary components liquid connecting pipe liquid closing valve gas co...

Page 16: ...ranty registration card If not filed or not filled completely or correctly your factory warranty may not be qualified Possible Problems or Consequences PRESSURE TABLES Warning R410A refrigerant bears...

Page 17: ...ments for the refrigerant R410A Do not use any refrigerant other than R410A Do not clean the unit using mineral oil WARRANTY AND TECH SUPPORT YMGI warrants to the purchaser owner s that YMGI products...

Page 18: ...t history No Date Service Maintenance Conducted Person Phone USER NOTES Put down whatever questions you have or problems you have seen as a unit history No Date Questions or Problems Remarks USER NOTE...