INSTALLATION-INDOOR UNIT

INSTALLATION-INDOOR UNIT

REFIT DRAIN HOSE FROM THE RIGHT TO THE LEFT SIDE     

If drain hose needs to be refitted from the original 
position (right side) to left side of the indoor unit, 
careful handling is very necessary. 

Refitting method: remove the drain hose from 
original position, without breaking hose. Unplug 
the plug at the left side. Apply water-resistant glue 
to fit the drain hose and the fitting before securing 
it.
Apply water-resistant glue onto the plug and fit it 
back into the condensate connection at right side. 

NOTES: May use some sort of clamp to double secure connections.

Alternative condensate 

connection at left side

Drain hose

HANG INDOOR UNIT 

Run copper set/wire cables/drain hose through the 
wall hole and hang the indoor unit onto the 
mounting plate (place the hook on the mounting 
plate into the hanging rib at rear side of plastic 
casing).

Snap the plastic casing bottom into the mounting 
plate, gently .

To drain the condensate easily, the drain hose should be inclined downward (pitched towards drain direction 
1/4" per foot).
Figures below from the 2nd to 5th show some incorrect practices.

Drain hose may be extended using the hose coming with the installation list.

SHAPE THE DRAIN HOSE

STUFF AND SEAL THE HOLE FOR COPPER LINE SET/WIRE CABLE/DRAIN HOSE 

* Use putty to seal the wall hole.

* Use clamp (pipe fastener) to secure the pipe at specified position.

>18"

>18"

Other Brackets

Heavy-Duty PVC Riser

for Ground Mounting

Coated Brackets 
with Accessories       

Bracket Accessories

(Optional) 

Strongly suggest to install the outdoor unit above the ground either on platform or brackets as shown below. 

Heat pump unit must be lift up from ground level, since condensate must be drained out of the drain pan in 
condensing unit; othewise, 

condensate may ice up causing damage to the condensing unit.

Suggest to use YMGI-provided brackets and condensate drainage fitting accessories.

Indoor unit
front

Bottom

the rib of indoor unit

the mounting plate

Slice the 
insulation 
before 
bending.     

Hold the 90 
degree bend 
root, bend one 
tube one time, 
slowly, no 
quicker than 
10 seconds/
90 degree 
bend.

* If pipes need to come out of the rear side (facing 
  the front of indoor unit) of the indoor unit, no need 
  to snap off anything.

* If pipes need to be rerouted to a different direction 
  from the one preset at factory (towards left side, if 
  facing the front cover of indoor unit), lay down the 
  indoor unit on soft cushion or foam. Don't rub the 
  plastic casing.

* In order to keep from pipe damage, need to bend 
  the copper tubing set gently and slowly (finish 
  bending no less than 10 seconds/90 degree), by 
  holding at the root of the original 90 degree bend 
  nicely and firmly. Don't rub two copper lines during 
  bending. Better to cut off the insulation and bend 
  the two pipes one by one, not two together.

PREPARE INDOOR UNIT- COPPER LINE SET/DRAIN HOSE

INSTALL DRAIN PIPE AT INDOOR

The drain hose must be placed beneath the copper 
pipes and MUST NOT be hunched or bended 
sharply.                                                 

Do not pull the drain hose too hard, otherwise it 
may get broken.

Before passing drain hose through the hold, wrap 
with insulation to keep from possible damage.

The copper pipe and the drain hose must be 
wrapped by piping wrap. 

Insulation pad should be used where the pipe 
contacts the wall.

Drain hose coming with indoor unit

Drain hose extending to drain line

2 in or less
from floor

dip hose in water

water 
leak

standing
water

air

water 
leak

rise up

water 
leak

decline 
downward

Sealed with putty

Secure the piping/
wiring set with clamp

Trim the extra portion

Indoor unit

Screw

Clamp

INSTALLATION-OUTDOOR UNIT

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

Summary of Contents for WMMS-09C-V2A/B(58) 2

Page 1: ...red free from defects in material and workmanship for normal use and maintenance Installation operation maintenance and service shall follow professional practices for regular cooling and heating equipment NEC State City or Local Codes and related manuals from YMGI Otherwise damage to equipment or property and even injury to people may occur Installer Currently licensed HVAC technician only Read m...

Page 2: ... differ from manufacturer to manufacturer and model to model Any ignoring or negligence may cause unit failure or damage which could be irrevocable and permanent 5 All of YMGI s products are fully tested and have passed rigorous safety and performance standards and others related to the industry before being packed and shipped YMGI only uses famous brands as suppliers for their parts that are also...

Page 3: ...es and wires are to be installed 11 If all the suggestions have been taken and all the necessary steps are followed CUSTOMER AND TECHNICIAN MUST READ The cost of not having your unit installed properly can be more expensive than spending the little extra money that hiring the right contractor will cost Protect your investment and warranty eligibility by doing it right the first time THE FOLLOWING ...

Page 4: ...trical power V Ph Hz measured at wiring terminal block of Indoor unit outdoor unit 7 Wire gauge length and terminal colors between circuit breaker disconnect switch to outdoor unit 9 The size of HVAC circuit breaker fuse or disconnect switch to the outdoor unit 11 What is the refrigerant pipe length between each indoor unit and the outdoor unit Unit A Unit B Unit C Unit D 13 What is the elevation ...

Page 5: ...erience or professional knowledge to correct the problem RECEIVING AND FREIGHT DAMAGE ATTENTION Freight package unit shall be checked thoroughly for damage at receiving before accepting by signing on the carrier s delivery paperwork Upon shipment being signed for acceptance it becomes a binding document as to the condition of the products on delivery We cannot process any shipping damage claim if ...

Page 6: ...y help you in the following steps in sequence from 1 to 3 CUSTOMER AND TECHNICIAN MUST READ If the damage is minor or partial that you choose to accept you can contact the distributor or YMGI to discuss the possible replacement of the damaged part If refusal of the shipment is needed due to severe freight damage DO NOT sign the carrier s delivery receipt document indicating that you accept the pro...

Page 7: ...send to you the Customer Request to Ship Products to YMGI Service Center for Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to the YMGI Group 3 Once the form has been completed and sent back to YMGI remove the units and ship back to YMGI Please make a note describing the problem and communication history if pos...

Page 8: ...ns of general up flow condensing units are limited such as apartments condos lofts multi families and high rise buildings and others named or unnamed a Indoor unit s delivers the thermal and acoustical comfort to the rooms Air is drawn through the coil from the front or topside and then discharged from the bottom In cooling mode air passing through coil is cooled in heating mode air passing throug...

Page 9: ... copper tube Aluminum fin copper tube Axial flow Axial flow T1 T1 1 4 1 4 5 8 5 8 I IP24 560 170 Automatic Defrosting Automatic Defrosting WMMS 30C V2B 58 2 WMMS 36C V2B 58 2 MITSUBISHI MITSUBISHI 125 125 25 25 2860 2860 50 60 50 60 Cross flow fan 1 Aluminum fin copper tube 0 28 2 2 PCB 3 15A Transformer 0 2A PCB 3 15A Transformer 0 2A 52 50 48 40 52 50 48 40 62 60 58 50 62 60 58 50 Aluminum fin c...

Page 10: ...led on a wall or balcony close to the indoor unit the following are some benefits for contractors and customers Each system is thoroughly tested before leaving the factory Each unit is acoustically thermally and systematically designed to give optimum quality and reliability P17 OF 38 INDOOR UNIT MAJOR COMPONENTS Remode Control Display Auto Directional Louvers Up and Down Test Reset Switch Front P...

Page 11: ...12K 18K 24K Unit W 30 30 35 0 36 2 D1 12 6 21 3 11 3 12 6 21 3 11 3 15 6 22 0 24 0 11 5 15 7 16 8 D 10 1 10 1 13 4 14 6 P20 OF 38 USER NOTES AND SERVICE LOG 6 6 12 100 6 20 12 6 20 18 21 11 INSTALLATION CLEARANCE REQUIREMENTS GENERAL 155 163 161 170 31 3 31 3 30K 36K 38 5 38 5 16 8 16 8 YMGI Engineered Comfort Products for A Sustainable and Efficient Green World YMGI Engineered Comfort Products fo...

Page 12: ...g Tape Level Flash Light Screw Driver Phillps and Flat Hammer Knife Scissors Goggled Glass Mask Gloves Ladder 2 Refrigeration Related Work RECOMMENDED TOOLS FOR INSTALLATION 3 Electrical Related Installation Wire Cutter Wire Stripper Sharp Plier Cable Ties Black Tape for Electrical Use Meter Electrical Clamp Meter Not Shown Manifold Infra Thermometer Not Shown 4 Trial Running Units and Inspection ...

Page 13: ... are to be used make sure to keep the two holes close to each other at least 2 inches apart Mounting plate should be attached to the structural part of the wall Minimum clearance as shown below is required in order to ensure proper airflow and enough service room INSTALL WALL MOUNT PLATE Check unit to make sure the unit is good shape and ready to install in Check unit to make sure the installation...

Page 14: ... in condensing unit othewise condensate may ice up causing damage to the condensing unit Suggest to use YMGI provided brackets and condensate drainage fitting accessories Indoor unit front Bottom the rib of indoor unit the mounting plate Slice the insulation before bending Hold the 90 degree bend root bend one tube one time slowly no quicker than 10 seconds 90 degree bend If pipes need to come out...

Page 15: ... perpendicular to the pipe surface Don t cut too fast or too hard Turn and tighten the tube cutter slowly Remove residual left and de bur at the cutting edge The cutting edge should be clear and clean and smooth Running Interconnection Refrigerant Lines Use clean refrigeration grade of copper pipe only Keep the copper lines from kinking and transmitting noise to walls cabinets etc Pipe length not ...

Page 16: ...nation securely on the external wall with proper clamps at 6 feet apart Fill the gap between the wall hole and wall sleeve with putty to keep from rain or dust entering inside PIPING GUIDE Set the packed pipes vertically and then slowly unwind Don t unwind only one end of the coiled pipes Use pulley to keep the safe bending radius May also use rolling wheel to reduce internal pipe tension and avoi...

Page 17: ...efrigerant Charge Level Reference Temperature Pressure Table Split Condensing Unit R410A AC Product Series YMGI Group Mini Split Version 01 11 2010 Reference Temperature Pressure Table Split Condensing Unit R410A Heat Pump Product Series YMGI Group Mini Split System Version 01 11 2010 Outdoor Dry Bulb F Outdoor Dry Bulb C Outdoor Wet Bulb F Outdoor Wet Bulb C Indoor Dry Bulb Indoor Wet Bulb Discha...

Page 18: ...ng indoor fan motor works Heating all stop running 3s off blink four times 1 Forcibly lift up the panel at a specific angle from the two ends of the front panel following the arrow direction Then pull the air filter downwards to remove it Fig a 2 Mount the healthy filter onto the air filter Fig b If the air filter cannot be installed please mount the healthy filter on the front case Fig c 3 Mount ...

Page 19: ...ge is not staable cooling dehumidifying compressor will stop indoor fan motor works Heating all will stop 1 Check the Input voltage if the Voltage is lower than 150VAC restart the machine when the power supply is normal 2 Checking the reactor L connection off 3s blink 21 times PL Low DC Bus voltage protection Outdoor temp sensor hasn t connected well or damaged please refer to the sensor resistanc...

Page 20: ... the unit and or know more details than anybody else They will check the unit and find out the problems with the professional knowledge about HVAC and electric product installation by using special tools or instrument They can contact YMGI technical support for technical help during unit installation or inspection Product model and serial numbers needed which can be found on unit nameplate sticker...

Reviews: