YMGI WMMS-09C-V2A/B(58) 2 Installation Instructions Manual Download Page 18

UNIT MAINTENANCE & 

SER

VICE GUIDE

INST

ALLER'S 

INSTRUCTION

TROUBLE SHOOTING

P33 OF 38

INSTALLATION AND MAINTENANCE OF ENHANCED FILTER

CONFIRMATION

1) Power Connection

    Check and confirm that the power breaker of proper size is installed and can operates (ON/OFF) normally.

2) Power Voltage

    Check and confirm that power voltage is AC 208-230V

10%. If power voltage is not falling  in this range, the 

    unit may not operate properly and damage may be caused.

FLASHING LED OF INDOOR/OUTDOOR UNIT AND PRIMARY JUDGEMENT

P34 OF 38

Take out the (enhanced) filter before cleaning according to the installation instruction. Pay special attention tthat
silver ion filter can't be cleaned with water, while active carbon, photo catalyst, low temperature conversion (LTC) 
catalyst, formaldehyde eliminator, ca-techin or mite killing filter can (but can't be cleaned with brush or hard/sharp
tools). Dry and reinstall it after cleaning. Make sure to replace securely and properly.

CLEANING AND MAINTENANCE (Regular Filter and/or Other Enhanced Filters)

FILTER LIFETIME

The washable filter will last a long time. But some (enhanced) filters may only have a lifetime   about one year 
under normal 

. As far as  the silver ion filter, it will 

 invalid when its surface becomes 

of

conditions

become

black (green).

INSTALLATION INSTRUCTIONS

No.

Indoor unit display

Double 8 display

Indicator display (LED 
blinks 0.5s-ON/0.5s-
OFF)

Running 
LED

Cooling 
LED

Heating 
LED

D40 D41 D42 D43

Outdoor unit 
display (LEDs 
have 3 status)

Unit actions

Possible clauses 

(Primary judgement)

High pressure of system, might be:
1) Refrigerant is too much;
2) Poor heating exchanging for units 
    (including heat exchanger is dirty 
    and unit heating radiating ambient 
    is poor);
3) Ambient temp. is too high.

E1

E2

Cooling, dehumidifying, except the 
indoor fan motor is running, others 
will stop running. 

Cooling, dehumidifying: compressor, 
outdoor fan motor will stop running, 
indoor fan motor will keep running.

1) Poor indoor unit air returning;
2) indoor fan motor rotating speed 
    abnormal;
3) Evaporator ailter is dirty.

3s off 
blink 
once

3s off 
blink 
twice

1

2

Pls refer to trouble shooting (air 
exhaust protection, overload)

3

E4

Cooling, dehumidifying: compressor, 
outdoor fan motor will stop running, 
indoor fan motor works. Heating: all 
stop running.

3s off 
blink 
four 
times

1) Forcibly lift up the panel at a specific angle from the two 
    ends of the front panel following the arrow direction. 
    Then pull the air filter downwards to remove it. (Fig.a)

2) Mount the healthy filter onto the air filter, (Fig.b). If the air 
    filter cannot be installed, please mount the healthy filter 
on the front case. (Fig.c)

3) Mount the air filter properly along the arrow direction in 
    Fig.d, and then close the panel cover.

TROUBLE SHOOTING

4

1) Power supply is not stable, 
    fluctuation is too much;
2) Power supply is too low, 
    overload is too much.

Cooling, dehumidifying: compressor, 
outdoor fan motor will stop, indoor 
fan will work. Heating: all will stop.

Off 3s 
blink 
5 times

E5

5

Please refer to trouble shooting.

Cooling: compressor will stop,
indoor fan motor works. Heating:
all will stop.

E6

Off 3s 
blink 
6 times

6

Please refer to trouble shooting.

Cooling: compressor will stop,
indoor fan motor works. Heating:
all will stop.

Off 3s 
blink 
8 times

E8

H6

Off 3s 
blink 
11 
times

Whole unit will stop to run.

1) Poor insert for GPF;
2) Indoor control board API 
    malfunction;
3) Indoor motor M1 malfunction.

7

C5

Off 3s 
blink 
15 
times

Whole unit will stop to run.

Indoor control board
APl jump cap poor connected,
please pull and then or replace
the jump cap.

8

1) Room temp. sensor is not 
    connected with the control 
    panel AP1;
2) Room temp. sensor is damaged.

Cooling, dehumidifying: indoor fan 
motor is running, other overloads
will stop. Heating: whole unit will 
stop to run.

Off 3s 
blink 
once

F1

9

Protection 
malfunction 
status

System high 
pressure 
protection

Anti-freezing 
protection

Compressor 
air exhaust 
high temp. 
protection

AC overload
protection

Indoor and 
outdoor units
communication 
malfunction

Anti-high tcmp.
protection

Indoor unit 
motor no 
feedback

Jump wire cap
mal function
protection

Indoor ambient
sensor open
circuit,
short circuit

Indoor 
evaporator
sensor circuit,
open, short 
circuit

F2

Off 3s 
blink 
twice

Cooling, dehumidifying: indoor fan 
motor running, other overload will 
stop. Heating: whole unit will stop.

1) Tube temp. sensor is not 
    connected with the control panel 
    AP1;
2) Tube temp. sensor is damaged.

10

Air filter 
enhanced

Ion carbon cold 
catalyst

Enhanced

Fig.a

Fig.b

Fig.c

Fig.d

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

Summary of Contents for WMMS-09C-V2A/B(58) 2

Page 1: ...red free from defects in material and workmanship for normal use and maintenance Installation operation maintenance and service shall follow professional practices for regular cooling and heating equipment NEC State City or Local Codes and related manuals from YMGI Otherwise damage to equipment or property and even injury to people may occur Installer Currently licensed HVAC technician only Read m...

Page 2: ... differ from manufacturer to manufacturer and model to model Any ignoring or negligence may cause unit failure or damage which could be irrevocable and permanent 5 All of YMGI s products are fully tested and have passed rigorous safety and performance standards and others related to the industry before being packed and shipped YMGI only uses famous brands as suppliers for their parts that are also...

Page 3: ...es and wires are to be installed 11 If all the suggestions have been taken and all the necessary steps are followed CUSTOMER AND TECHNICIAN MUST READ The cost of not having your unit installed properly can be more expensive than spending the little extra money that hiring the right contractor will cost Protect your investment and warranty eligibility by doing it right the first time THE FOLLOWING ...

Page 4: ...trical power V Ph Hz measured at wiring terminal block of Indoor unit outdoor unit 7 Wire gauge length and terminal colors between circuit breaker disconnect switch to outdoor unit 9 The size of HVAC circuit breaker fuse or disconnect switch to the outdoor unit 11 What is the refrigerant pipe length between each indoor unit and the outdoor unit Unit A Unit B Unit C Unit D 13 What is the elevation ...

Page 5: ...erience or professional knowledge to correct the problem RECEIVING AND FREIGHT DAMAGE ATTENTION Freight package unit shall be checked thoroughly for damage at receiving before accepting by signing on the carrier s delivery paperwork Upon shipment being signed for acceptance it becomes a binding document as to the condition of the products on delivery We cannot process any shipping damage claim if ...

Page 6: ...y help you in the following steps in sequence from 1 to 3 CUSTOMER AND TECHNICIAN MUST READ If the damage is minor or partial that you choose to accept you can contact the distributor or YMGI to discuss the possible replacement of the damaged part If refusal of the shipment is needed due to severe freight damage DO NOT sign the carrier s delivery receipt document indicating that you accept the pro...

Page 7: ...send to you the Customer Request to Ship Products to YMGI Service Center for Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to the YMGI Group 3 Once the form has been completed and sent back to YMGI remove the units and ship back to YMGI Please make a note describing the problem and communication history if pos...

Page 8: ...ns of general up flow condensing units are limited such as apartments condos lofts multi families and high rise buildings and others named or unnamed a Indoor unit s delivers the thermal and acoustical comfort to the rooms Air is drawn through the coil from the front or topside and then discharged from the bottom In cooling mode air passing through coil is cooled in heating mode air passing throug...

Page 9: ... copper tube Aluminum fin copper tube Axial flow Axial flow T1 T1 1 4 1 4 5 8 5 8 I IP24 560 170 Automatic Defrosting Automatic Defrosting WMMS 30C V2B 58 2 WMMS 36C V2B 58 2 MITSUBISHI MITSUBISHI 125 125 25 25 2860 2860 50 60 50 60 Cross flow fan 1 Aluminum fin copper tube 0 28 2 2 PCB 3 15A Transformer 0 2A PCB 3 15A Transformer 0 2A 52 50 48 40 52 50 48 40 62 60 58 50 62 60 58 50 Aluminum fin c...

Page 10: ...led on a wall or balcony close to the indoor unit the following are some benefits for contractors and customers Each system is thoroughly tested before leaving the factory Each unit is acoustically thermally and systematically designed to give optimum quality and reliability P17 OF 38 INDOOR UNIT MAJOR COMPONENTS Remode Control Display Auto Directional Louvers Up and Down Test Reset Switch Front P...

Page 11: ...12K 18K 24K Unit W 30 30 35 0 36 2 D1 12 6 21 3 11 3 12 6 21 3 11 3 15 6 22 0 24 0 11 5 15 7 16 8 D 10 1 10 1 13 4 14 6 P20 OF 38 USER NOTES AND SERVICE LOG 6 6 12 100 6 20 12 6 20 18 21 11 INSTALLATION CLEARANCE REQUIREMENTS GENERAL 155 163 161 170 31 3 31 3 30K 36K 38 5 38 5 16 8 16 8 YMGI Engineered Comfort Products for A Sustainable and Efficient Green World YMGI Engineered Comfort Products fo...

Page 12: ...g Tape Level Flash Light Screw Driver Phillps and Flat Hammer Knife Scissors Goggled Glass Mask Gloves Ladder 2 Refrigeration Related Work RECOMMENDED TOOLS FOR INSTALLATION 3 Electrical Related Installation Wire Cutter Wire Stripper Sharp Plier Cable Ties Black Tape for Electrical Use Meter Electrical Clamp Meter Not Shown Manifold Infra Thermometer Not Shown 4 Trial Running Units and Inspection ...

Page 13: ... are to be used make sure to keep the two holes close to each other at least 2 inches apart Mounting plate should be attached to the structural part of the wall Minimum clearance as shown below is required in order to ensure proper airflow and enough service room INSTALL WALL MOUNT PLATE Check unit to make sure the unit is good shape and ready to install in Check unit to make sure the installation...

Page 14: ... in condensing unit othewise condensate may ice up causing damage to the condensing unit Suggest to use YMGI provided brackets and condensate drainage fitting accessories Indoor unit front Bottom the rib of indoor unit the mounting plate Slice the insulation before bending Hold the 90 degree bend root bend one tube one time slowly no quicker than 10 seconds 90 degree bend If pipes need to come out...

Page 15: ... perpendicular to the pipe surface Don t cut too fast or too hard Turn and tighten the tube cutter slowly Remove residual left and de bur at the cutting edge The cutting edge should be clear and clean and smooth Running Interconnection Refrigerant Lines Use clean refrigeration grade of copper pipe only Keep the copper lines from kinking and transmitting noise to walls cabinets etc Pipe length not ...

Page 16: ...nation securely on the external wall with proper clamps at 6 feet apart Fill the gap between the wall hole and wall sleeve with putty to keep from rain or dust entering inside PIPING GUIDE Set the packed pipes vertically and then slowly unwind Don t unwind only one end of the coiled pipes Use pulley to keep the safe bending radius May also use rolling wheel to reduce internal pipe tension and avoi...

Page 17: ...efrigerant Charge Level Reference Temperature Pressure Table Split Condensing Unit R410A AC Product Series YMGI Group Mini Split Version 01 11 2010 Reference Temperature Pressure Table Split Condensing Unit R410A Heat Pump Product Series YMGI Group Mini Split System Version 01 11 2010 Outdoor Dry Bulb F Outdoor Dry Bulb C Outdoor Wet Bulb F Outdoor Wet Bulb C Indoor Dry Bulb Indoor Wet Bulb Discha...

Page 18: ...ng indoor fan motor works Heating all stop running 3s off blink four times 1 Forcibly lift up the panel at a specific angle from the two ends of the front panel following the arrow direction Then pull the air filter downwards to remove it Fig a 2 Mount the healthy filter onto the air filter Fig b If the air filter cannot be installed please mount the healthy filter on the front case Fig c 3 Mount ...

Page 19: ...ge is not staable cooling dehumidifying compressor will stop indoor fan motor works Heating all will stop 1 Check the Input voltage if the Voltage is lower than 150VAC restart the machine when the power supply is normal 2 Checking the reactor L connection off 3s blink 21 times PL Low DC Bus voltage protection Outdoor temp sensor hasn t connected well or damaged please refer to the sensor resistanc...

Page 20: ... the unit and or know more details than anybody else They will check the unit and find out the problems with the professional knowledge about HVAC and electric product installation by using special tools or instrument They can contact YMGI technical support for technical help during unit installation or inspection Product model and serial numbers needed which can be found on unit nameplate sticker...

Reviews: