YMGI WMMS-09C-V2A/B(58) 2 Installation Instructions Manual Download Page 15

INST

ALLER'S 

INSTRUCTION

INST

ALLER'S 

INSTRUCTION

P27 OF 38

P28 OF 38

CONNECT REFRIGERANT PIPES BETWEEN INDOOR AND OUTDOOR UNITS

Remove the wiring diagram cover where also the 
handle for moving unit is located.

Following the wiring diagrams on the unit or the wiring 
diagram manual that comes with the indoor unit to 
get familiar with 

 wiring and make sure 

. If there is any discrepancy, always 

use the 

.

the

everything 

is correct

diagram that is attached to the units

Connect wires between indoor unit and outdoor 
unit-power wire from outdoor to Indoor, control 
wires from Indoor unit to outdoor unit. Pass wire 
through certified wire pipes, harnesses and 
knockouts. Enough length shall be left for future 
service. Only copper wire is allowed.

Bring in line-voltage power input wires from circuit 
breaker to line-voltage wire terminal block at 
outdoor unit. Pass through certified wire pipes, 
harnesses and knockouts. Enough length shall be 
left for future service. Only copper wire is allowed.

Strictly follow NEC or state or local codes to select 
wires, circuit breaker, conduits and to perform 
installation work.

Disconnect switch box for outdoor unit

OUTDOOR WIRING: OUTDOOR-INDOOR UNIT & DISCONNECT SWITCH 
BOX/CIRCUIT BREAKER/FUSE

WIRING OUTDOOR UNIT

PIPING AND WIRING SIZES

INSTALLATION-OUTDOOR UNIT

INSTALLATION & PICTURES-WALL MOUNT BRACKET FOR OUTDOOR UNIT(S) 
(PART VARIES UPON MODELS/AVAILABILITY)

Select a secured location where the outdoor unit will be installed properly.

Orient the unit rear side (intake grill) towards wall and front side (discharge grill) away from wall.

For ground installation, use factory-provided riser and accessories. Not to bolt unit feet directly onto ground. 
Riser or brackets shall be levelled at outdoor unit foot surfaces. Secure unit foot by tightening bolts, nuts and 
anti-vibration pads.

(Actual unit/parts looking/installation may vary from the illustrated)

CONNECT WIRING BETWEEN OUTDOOR UNIT AND INDOOR UNIT 

* Check the nameplate for rated electrical data. Connect unit to the correct electrical power source.

O

O

* Select power wire of proper type and size. Suggest to use UL approved 105 C/221 F multi-strand copper wire 
  for outdoor use. Refer to the following tables, for proper selection of wire gauge, size and circuit breaker.

Non-Metalic Power Whip for Outdoor Use 

(Field-Supplied, Not Spliced and Not Knotted, 

Water-Proof Sealed Tight, UL Approved)

Firstly, connect copper tubes at indoor unit. Bend 
pipes by tools but not by hands. Extra length is 
needed for future service.

REFRIGERANT PIPES: 

For distance other than 25' between indoor and 
horizontal venting condensing units, refer to the 
following table for copper sizes.

Make sure the pipe section where is to be cut is 
straight and smooth. Apply cutting blade straightly 
perpendicular to the pipe surface. Don't cut too fast 
or too hard. Turn and tighten the tube cutter slowly. 
Remove residual left and de-bur at the cutting edge. 
The cutting edge should be clear and clean and 
smooth.

Running Interconnection Refrigerant Lines: 

Use clean refrigeration grade of copper pipe only. 
Keep the copper lines from kinking and transmitting 
noise to walls, cabinets, etc. Pipe length not to exceed
150', elevation not to exceed 35. Insulate both the 
liquid and gas copper lines with at least 3/8" thick 
insulation tubes. Band and tape and secure refrigerant 
lines. Support copper lines at proper distance apart to
keep tubes from sagging.

CUT REFRIGERANT PIPE:

 

Connect Copper Pipes-Flare/nut Connection at Both Indoor and Outdoor Units

Proper torque shall be applied to make good connection at female nut, flare and male nut, as recommended in 
the following table. Too much torque may damage and break flare/nut seal. Too less torque may not ensure 
good seal. ALWAYS use a pair of wrenches.

Flare Nut

1/4-3/8"

1/4-1/2"

1/2-3/4"

7/8-1 1/8"

Tightening Torque

25 Ft. LBs (350 Kgf.cm)

40 Ft. LBs (560 Kgf.cm)

60 Ft. LBs (840 Kgf.cm)

110Ft. LBs (1540 Kgf.cm)

Refrigerant Pipe Flare/Nut Connection Tightening Torque

Refrigerant Pipe Length and Height 

CONNECT REFRIGERANT PIPES

In this case, put wet rag to protect valves or other components from being overheated. When using flux, rub the 
tube surface using steel wool to shine and clean 

 dry 

and

in order to keep contamination from entering the system.

Connect Copper Pipes-Sweat Connection

Refrigerant Valve and Pipe Size/Length

K

Btu/h

09

12

18

Valve Size

Liq, Gas

1/4", 3/8"

1/4", 3/8"

1/4", 1/2"

15-30ft

1/4", 3/8"

1/4", 3/8"

1/4", 1/2"

31-60ft

1/4", 3/8"

1/4", 3/8"

1/4", 1/2"

Line Sizes at Different Length

1,000 Btu/h

09

12

18

 Height (Ft.)

3.82

3.6

3.8

Length (Ft.)

23

24.3

31.4

Cut too

hard

Cut too

hard/fast

Angle

Inclined

Twist to cut pipe

O

90

Bad cut

De-burring tool

Fixed

Need to properly 

select dimensions A per D

Pipe flare 
expander

Canter line

Canter line

Expander 
Head

Copper line

Model  Liquid/Gas 

Line 

Min/Max.Length/
+/-Elevation 

Power Wire Min. 

Disconnect Switch Box to 
Outdoor Unit 

Power/ Control Wire Min. 

Outdoor to Indoor Unit 

Recommended HVAC 
Circuit Breaker/Fuse 
AMP 

(to Outdoor Unit) 

09K 

1/4" & 3/8" 

15/70  /35/45 

L/N/G, 115/1/60, 12AWG 

N(1)/2/3/G, 115/1/60, 16AWG 

20/30

12K 

1/4" & 3/8" 

15/75  /35/45  

L/N/G, 115/1/60, 12AWG 

N(1)/2/3/G, 115/1/60, 16AWG 

20/30

18K 

1/4" & 1/2" 

15/100/50/60

L1/L2/G, 208-230/1/60, 10AWG  N(1)/2/3/G, 208~230/1/60, 16AWG 

20

24K 

30K 

36K 

1/4" & 5/8" 

1/4" & 5/8" 

1/4" & 5/8" 

15/100/50/60

15/125/50/60

15/125/50/60

L1/L2/G, 208-230/1/60, 10AWG 

L1/L2/G, 208-230/1/60, 8AWG 

L1/L2/G, 208-230/1/60, 8AWG 

N(1)/2/3/G, 208~230/1/60, 16AWG 

N(1)/2/3/G, 208~230/1/60, 16AWG 

N(1)/2/3/G, 208~230/1/60, 16AWG 

30

30

40

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

For ground installation, 

it is recommended to use YMGI optional accessories like risers.

Summary of Contents for WMMS-09C-V2A/B(58) 2

Page 1: ...red free from defects in material and workmanship for normal use and maintenance Installation operation maintenance and service shall follow professional practices for regular cooling and heating equipment NEC State City or Local Codes and related manuals from YMGI Otherwise damage to equipment or property and even injury to people may occur Installer Currently licensed HVAC technician only Read m...

Page 2: ... differ from manufacturer to manufacturer and model to model Any ignoring or negligence may cause unit failure or damage which could be irrevocable and permanent 5 All of YMGI s products are fully tested and have passed rigorous safety and performance standards and others related to the industry before being packed and shipped YMGI only uses famous brands as suppliers for their parts that are also...

Page 3: ...es and wires are to be installed 11 If all the suggestions have been taken and all the necessary steps are followed CUSTOMER AND TECHNICIAN MUST READ The cost of not having your unit installed properly can be more expensive than spending the little extra money that hiring the right contractor will cost Protect your investment and warranty eligibility by doing it right the first time THE FOLLOWING ...

Page 4: ...trical power V Ph Hz measured at wiring terminal block of Indoor unit outdoor unit 7 Wire gauge length and terminal colors between circuit breaker disconnect switch to outdoor unit 9 The size of HVAC circuit breaker fuse or disconnect switch to the outdoor unit 11 What is the refrigerant pipe length between each indoor unit and the outdoor unit Unit A Unit B Unit C Unit D 13 What is the elevation ...

Page 5: ...erience or professional knowledge to correct the problem RECEIVING AND FREIGHT DAMAGE ATTENTION Freight package unit shall be checked thoroughly for damage at receiving before accepting by signing on the carrier s delivery paperwork Upon shipment being signed for acceptance it becomes a binding document as to the condition of the products on delivery We cannot process any shipping damage claim if ...

Page 6: ...y help you in the following steps in sequence from 1 to 3 CUSTOMER AND TECHNICIAN MUST READ If the damage is minor or partial that you choose to accept you can contact the distributor or YMGI to discuss the possible replacement of the damaged part If refusal of the shipment is needed due to severe freight damage DO NOT sign the carrier s delivery receipt document indicating that you accept the pro...

Page 7: ...send to you the Customer Request to Ship Products to YMGI Service Center for Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to the YMGI Group 3 Once the form has been completed and sent back to YMGI remove the units and ship back to YMGI Please make a note describing the problem and communication history if pos...

Page 8: ...ns of general up flow condensing units are limited such as apartments condos lofts multi families and high rise buildings and others named or unnamed a Indoor unit s delivers the thermal and acoustical comfort to the rooms Air is drawn through the coil from the front or topside and then discharged from the bottom In cooling mode air passing through coil is cooled in heating mode air passing throug...

Page 9: ... copper tube Aluminum fin copper tube Axial flow Axial flow T1 T1 1 4 1 4 5 8 5 8 I IP24 560 170 Automatic Defrosting Automatic Defrosting WMMS 30C V2B 58 2 WMMS 36C V2B 58 2 MITSUBISHI MITSUBISHI 125 125 25 25 2860 2860 50 60 50 60 Cross flow fan 1 Aluminum fin copper tube 0 28 2 2 PCB 3 15A Transformer 0 2A PCB 3 15A Transformer 0 2A 52 50 48 40 52 50 48 40 62 60 58 50 62 60 58 50 Aluminum fin c...

Page 10: ...led on a wall or balcony close to the indoor unit the following are some benefits for contractors and customers Each system is thoroughly tested before leaving the factory Each unit is acoustically thermally and systematically designed to give optimum quality and reliability P17 OF 38 INDOOR UNIT MAJOR COMPONENTS Remode Control Display Auto Directional Louvers Up and Down Test Reset Switch Front P...

Page 11: ...12K 18K 24K Unit W 30 30 35 0 36 2 D1 12 6 21 3 11 3 12 6 21 3 11 3 15 6 22 0 24 0 11 5 15 7 16 8 D 10 1 10 1 13 4 14 6 P20 OF 38 USER NOTES AND SERVICE LOG 6 6 12 100 6 20 12 6 20 18 21 11 INSTALLATION CLEARANCE REQUIREMENTS GENERAL 155 163 161 170 31 3 31 3 30K 36K 38 5 38 5 16 8 16 8 YMGI Engineered Comfort Products for A Sustainable and Efficient Green World YMGI Engineered Comfort Products fo...

Page 12: ...g Tape Level Flash Light Screw Driver Phillps and Flat Hammer Knife Scissors Goggled Glass Mask Gloves Ladder 2 Refrigeration Related Work RECOMMENDED TOOLS FOR INSTALLATION 3 Electrical Related Installation Wire Cutter Wire Stripper Sharp Plier Cable Ties Black Tape for Electrical Use Meter Electrical Clamp Meter Not Shown Manifold Infra Thermometer Not Shown 4 Trial Running Units and Inspection ...

Page 13: ... are to be used make sure to keep the two holes close to each other at least 2 inches apart Mounting plate should be attached to the structural part of the wall Minimum clearance as shown below is required in order to ensure proper airflow and enough service room INSTALL WALL MOUNT PLATE Check unit to make sure the unit is good shape and ready to install in Check unit to make sure the installation...

Page 14: ... in condensing unit othewise condensate may ice up causing damage to the condensing unit Suggest to use YMGI provided brackets and condensate drainage fitting accessories Indoor unit front Bottom the rib of indoor unit the mounting plate Slice the insulation before bending Hold the 90 degree bend root bend one tube one time slowly no quicker than 10 seconds 90 degree bend If pipes need to come out...

Page 15: ... perpendicular to the pipe surface Don t cut too fast or too hard Turn and tighten the tube cutter slowly Remove residual left and de bur at the cutting edge The cutting edge should be clear and clean and smooth Running Interconnection Refrigerant Lines Use clean refrigeration grade of copper pipe only Keep the copper lines from kinking and transmitting noise to walls cabinets etc Pipe length not ...

Page 16: ...nation securely on the external wall with proper clamps at 6 feet apart Fill the gap between the wall hole and wall sleeve with putty to keep from rain or dust entering inside PIPING GUIDE Set the packed pipes vertically and then slowly unwind Don t unwind only one end of the coiled pipes Use pulley to keep the safe bending radius May also use rolling wheel to reduce internal pipe tension and avoi...

Page 17: ...efrigerant Charge Level Reference Temperature Pressure Table Split Condensing Unit R410A AC Product Series YMGI Group Mini Split Version 01 11 2010 Reference Temperature Pressure Table Split Condensing Unit R410A Heat Pump Product Series YMGI Group Mini Split System Version 01 11 2010 Outdoor Dry Bulb F Outdoor Dry Bulb C Outdoor Wet Bulb F Outdoor Wet Bulb C Indoor Dry Bulb Indoor Wet Bulb Discha...

Page 18: ...ng indoor fan motor works Heating all stop running 3s off blink four times 1 Forcibly lift up the panel at a specific angle from the two ends of the front panel following the arrow direction Then pull the air filter downwards to remove it Fig a 2 Mount the healthy filter onto the air filter Fig b If the air filter cannot be installed please mount the healthy filter on the front case Fig c 3 Mount ...

Page 19: ...ge is not staable cooling dehumidifying compressor will stop indoor fan motor works Heating all will stop 1 Check the Input voltage if the Voltage is lower than 150VAC restart the machine when the power supply is normal 2 Checking the reactor L connection off 3s blink 21 times PL Low DC Bus voltage protection Outdoor temp sensor hasn t connected well or damaged please refer to the sensor resistanc...

Page 20: ... the unit and or know more details than anybody else They will check the unit and find out the problems with the professional knowledge about HVAC and electric product installation by using special tools or instrument They can contact YMGI technical support for technical help during unit installation or inspection Product model and serial numbers needed which can be found on unit nameplate sticker...

Reviews: