YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

DESIGN OF DRAINAGE PIPELINE

1) The drainage pipeline should be kept at a certain gradient (1/50~1/100) so as to avoid bulges of pipes where 
    there might be water bends.

2) The drainage pipeline is form of the hard PVC pipes for common purposes which can be purchased locally. 
    The diameter of the PVC pipes is not less than 31mm and the pipeline should be fixed as close to the BU 
    module as possible.

3) Insert the drain hose into the drain hole of drainage pipeline. Use binding band to fix it tightly. It is not allowed 
    to use adhesive glue to join the drain hose to the drainage hole.

4) When the drainage pipeline is laid for a couple of units, the position of the shared pipeline should be 
    approximately 3.94inch lower than the drainage hole of each module. In this case, some special-purpose pipes 
    with thicker walls will be used.
5) At intervals of about 1 meter, fix the drain pipes to the wall with brackets, not floating in the air.

INSTALLATION OF PROTECTIVE LAYER ON CONNECTION PIPE

1) The refrigerant pipes should be insulated by the 
    insulating material and plastic tape in order to 
    prevent water condensation and leakage.

2) Do not use the foam on the branch pipe as the 
    material for heat insulation.
3) The joints of the system should be wrapped with 
    the insulating material and no gap is allowed on 
    the joint of the system, as shown in Fig.24.

4) Bundle the refrigerant pipe and transmission line 
    together with tape, and separate them from the 
    drain pipe to prevent the condensate water overflowing.

5) Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where it enters the wall. During the 
    wrapping, the later circle should cover half of the former one.

6) At intervals of about 1 m eter, fix the refrigerant pipes to the wall with brackets, that is, don't let the unit 
    withstand the weight of it or float it in the air.

O

* After the pipe is protected well enough, never bend it to form a small angle(<90 ), otherwise it would crack or 
  break.

* Do not wrap the refrigerant pipes very tight, otherwise the insulation effect would be weakened. Additionally, 
  make sure the drain hose is separated from the refrigerant pipes.

* After that, cover the hole on the wall with sealing materials to prevent wind and noise going into the room.

INSTALLATION OF DRAIN HOSE

DESIGN OF DRAINAGE PIPELINE

1) Choose one drain hole in the bottom of the outdoor unit.

2) Connect the drain hose to the drain hole.

3) The drain hose should be kept at 5~10 degrees of gradient to facilitate discharge 
    of the condensing water. Take care that does not exert too much force on the hose.

4) Thermal insulation materials should be placed at the joints of the drain 
    hose so as to prevent from dew condensation. Fix the drain hose firmly by 
    binding band.

5) The end of the drain hose should be inserted into the hole of drainage pipeline.

P19 OF 32

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

* The yellow-green wire of the air conditioner is the ground wire and must be fixed by the tapping screw. And it 
  cannot be used for other purpose or cut off. Otherwise, it will cause the hazard of electric shock.

* The reliable ground terminal should be provided and the ground wire cannot be connected to any of the 
  following places: a) Water pipe; b) Coal gas pipe; c) Sewage pipe; d) Lightning rod; e) Telephone line; f)Other 
  unreliable places considered by a professional.

ELECTRICAL WIRING WORK

* The ground connection should be reliable and the ground wire should be connected to the dedicated device of 
  the building by the professional.

* The electric installation should be carried out by the professional as instructed by the local laws, regulations 
  and also this manual.
* The air switch coupled with the leakage current protection switch must be equipped in the circuits, which is of 
  enough capacity and of both magnetic and thermal tripping functions in case of the short circuit and overload.

* The power supply of the outdoor unit and all the BU modules should be separately.

* The electrical work should use a cable length enough to cover the entire distance with no connection. If it is 
  unavoidable, please make sure the connection should be reliable and the external forces will not act on the 
  wires. Otherwise it will cause electrical shock or fire etc.
* The power cable with the rated voltage and exclusive circuit for the air conditioning should be used.

* Do not pull the power cable by force.

* The diameter of the power cable should be large enough and once it is damaged, it must be replaced by the 
  dedicated one.

1) Use a wire stripper to strip off about 0.1inch of the 
    insulation layer at the end of the wires;

2) Loosen the screws on the terminal block of the air 
    conditioner;
3) Use the pliers to bend the end of the wire into a ring 
    shape corresponding the size of the screw;

4) Pass the screw through the wire ring and fix it onto the 
    terminal block.

1) Knock the holes in the plate of the chosen direction with the hammer.

2) Place the rubber ring on the knockout hole.

3) Let the power cable and transmission line go through the knockout hole.

4) Connect the power cable of the outdoor unit to the L1, L2 terminals with the sign of the XT1 and as well as the 
    ground screw.

5) Connect the transmission line of the outdoor unit to the N(1), 2 terminals with the sign of the XT2.

6) Fix the power cable and transmission line firmly by cable fixing clip.

7) Screw the coping plate, front side plate, right connection board, front connection board back.

8) Cover the through-holes with sealing materials to prevent the water, dust or small animals going into the 
    outdoor unit.

* The transmission line and the power cable must be separated and separated with an interval of at least 2cm; 
  otherwise it may be result in communication problem.
* In order to protect the power cable and transmission line from damaging by the hole, the rubber ring must be 
  placed on the hole. Otherwise, it may cause electrical shock or fire etc.

* The power wire and transmission line must be more than one meter away from televisions or radios which can 
  emit electromagnetic waves to prevent image interference or noise. Otherwise, the unit maybe cannot work.

* Confirm the each cable connected to the terminal screw is exactly and securely after finishing the electric work.

* Fix each ground wire separately with the ground screw.

* If the connecting wire is connected to the terminal incorrectly, the unit will not work normally.

PRECAUTIONS ON THE ELECTRICAL WIRING WORK

PRECAUTION OF LAYING WIRES

PROCEDURES FOR ELECTRICAL WIRING WORK

0.1

INST

ALLER'S 

INSTRUCTION

INST

ALLER'S 

INSTRUCTION

Summary of Contents for SYMPHONY CHOIR 80CH

Page 1: ... Installation operation maintenance and service shall follow professional practices for regular cooling and heating equipment NEC State City or Local Codes and related manuals from us Otherwise damage to equipment or property even injury to people may occur Installer Currently licensed HVAC installer only Read this manual before installation Sign on the warranty registration card User Keep this ma...

Page 2: ...ORTANT NOTE YMGI HOLDS FINAL EXPLANATION The quality of the installation plays a key role in whether the units will work well and for an extended period of time The information we provide in our manuals is for the sole purpose of reminding you and your installer It is our ultimate goal to help insure that your YMGI units are installed properly and correctly from the very beginning to the very end ...

Page 3: ...re humidity ranges installation operation maintenance service warranty parts and so on 4 Properly select correct most suitable YMGI product models of units and accessories for your HVAC applications jobs and list them in your proposal quote in writing on your company s quote form or letter head basing upon the information you get from 1 2 and 3 above 5 List your currently valid HVAC license and EP...

Page 4: ... the installation 5 Supply electrical power V Ph Hz measured at wiring terminal block of Indoor unit outdoor unit 7 Wire gauge length and terminal colors between circuit breaker disconnect switch to outdoor unit 9 The size of HVAC circuit breaker fuse or disconnect switch to the outdoor unit 11 What is the refrigerant pipe length between each indoor unit and the outdoor unit Unit A Unit B Unit C U...

Page 5: ... the tools to do these calculations correctly and get your approval before purchasing the air conditioner or heat pump equipment Any problems due to improper installing of the air conditioner heat pump system Installation should be conducted by currently licensed HVAC technician following manufacturer installation instructions all governing safety codes with care and professionalism Any problems d...

Page 6: ...the appointed service center A place which is full of machine oil A region with saline sodic soil near the sea A place where the sulphide fog exists such as the sulphur spring A place where the high frequency facilities exist such as radio equipment electric welder and medical equipment An environment with special conditions 1 When the place of the installation is exposed to strong wind When stron...

Page 7: ...is strength and level so that the unit will not cause any operating vibration or noise after installation 2 In accordance with the foundation drawing in the Fig 6 please drill 4 holes in the installation location A Discharge air side B Bottom view inches C Drain holes 3 Fix the unit securely with the foundation bolts You can get the M10 or M8 foundation bolts nuts and washers from the market 4 Rub...

Page 8: ...RANT PIPES Y type branch pipe must be installed in vertical or horizontal direction In the inlet of the branch pipe keep at least 19 69inch straight pipe 1 Pipe connections should be follow the following rules Outdoor unit shall be installed close to the indoor unit hence to minimize the length and bends of connection pipes The gap of outdoor unit and indoor units should be as small as possible Th...

Page 9: ...e operation 2 As shown in the following figure expel the gas from the refrigerant pipes by the vacuum pump 3 Open the pump and turn on the knobs to evacuate the gas in the liquid and gas pipes 4 When the pressure of the system is less than 0 1Mpa 1bar keep the system for more than one hour under the condition 5 Then turn off the knobs and the pump and if the pressure of the pressure vacuum gauge d...

Page 10: ...sure vacuum gauge 6 7 8 9 Hi knob Lo knob R410A tank Scale When the liquid and gas stop valves have not been opened the system is under the vacuum 1 Refer to the left of the Fig 20 connect the R410A tank to the system 2 Turn on the R410A tank and the Hi knob charge the R410A refrigerant into the system from the liquid side stop valve The Lo knob should be closed completely 3 Turn off the R410A tan...

Page 11: ...ground terminal should be provided and the ground wire cannot be connected to any of the following places a Water pipe b Coal gas pipe c Sewage pipe d Lightning rod e Telephone line f Other unreliable places considered by a professional ELECTRICAL WIRING WORK The ground connection should be reliable and the ground wire should be connected to the dedicated device of the building by the professional...

Page 12: ... or outdoor unit is blocked Remove the obstacles Air inlet or outlet of indoor unit or outdoor unit is blocked Remove the obstacles Temperature setting is improper Adjust the setting of remote controller or wire controller Air speed is set too low Adjust the setting of remote controller or wire controller Improper airflow direction Adjust the setting of remote controller or wire controller Door or...

Page 13: ... board of the outdoor unit Check for more details about the meaning of each error Conditions Causes When restart the unit soon after it is stopped The overload protection switch of the unit let the startup delayed for three minutes As soon as power supply is on The unit will stand by for approximate one minute When the cooling operation starts The hi humidity air indoor is cooled quickly The unit ...

Page 14: ...ing to include a 1 year installation service warranty at no extra charge Check with them to see if that is available If available include that in the contract 14 Verify and confirm the installation is done completely and all the unit functions have been checked and are working properly all the items in the checklist have been checked and marked well in the warranty registration card form prior to ...

Page 15: ...e exceptions Most have resulted in equipment failure due to lack of knowledge and experience A few of the problems result from DIY s lack of knowledge in the following areas Sizing and selecting correct type size and model of cooling and or heating equipment Sizing and installing correct electric circuit breakers and wires Wiring the units correctly and properly Taping the ends connecting to indoo...

Page 16: ...different from what are typical in traditional split type air conditioning and heat pump systems and similar systems made by other manufacturers These are not defects Take some time to learn the functions of your unit We will be happy to assist you with any questions you may have concerning the functions of your new unit 1 Part repair or replacement after trouble shooting This is the most common a...

Page 17: ...ND INSTALLATION SERVICE MAINTENANCE NOTES Notes Asked for Your Technician for Help Did You Ask YMGI Tech for Help INSTALLATION NOTES Original Installation Company Name Technician Name Phone HVAC License Job Not Performed by Technician Technician Checklist Completed Fully SERVICE MAINTENANCE NOTES No Date Contents of Service Maintenance Technician s Company Name Technician Name Phone HVAC License P...

Reviews: