Yes Falcon-II Operation Manual Download Page 15

15 

5.2  DETAILED OPERATING INSTRUCTIONS, CONT’D….. 
 

5.22  OPERATION - MODE ADJUSTMENT, CONT’D….. 

 

3.0 OUTSIDE Mode 

 
NOTE: Ventilation Rate 
 

Ventilate rate represents how much air is introduced into the indoor space from the 
outside.  Low  values  indicate  low  ventilation  rates  and  potentially  poor  air  quality. 
High levels indicate excessive ventilation and potential excessive energy usage.

  

 
To obtain an accurate measurement, readings should be taken 2~3 hours after 
occupancy has stabilized in a space or at a peak in daily CO2 concentrations

 
With indoor air quality control, CO2 value is an indicator of ventilation rate.

  400  ppm 

(Parts  Per  Million)  is  the  default  CO2  concentration  outside 

(according  to    

ASHRAE:  American  Society  of  Heating,  Refrigeration  and  Air  conditioning          
Engineers). 
 
3.1. Press the Mode button (

⑤), 

until OUTSIDE flashes. 

3.2. Press Enter (

②), 

to show OUTSIDE CO2 and PPM flashes. Press Up/Down (

④/

 

③) 

to adjust the reading.   

3.3.  Press  the  Enter  (

②), 

save  the  setting  and  return  to  the  User  Mode.  After       

 

modification, the VENT Rate will change. 

 

 
4.0 CALI Mode 

 
The  CO2  monitor  has  been  calibrated  at  the  factory  and  should  be  recalibrated 
every 12-months with a specified concentration of CO2. Sensor drift usually occurs 
in linearity. To perform calibration, follow the steps below. 
 

4.1.  If  battery  icon  shows  low  power,  replace  batteries  before  attempting  to       

 

calibrate or use AC adapter. 

4.2. Press the Mode button (

⑤), 

until CALI flashes. 

4.3. Press Enter (

②), 

“CALI” is shown on the display  

4.4. Adjust the lower display to ambient CO2  value by pressing the Up/Down (

④/

 

③) 

Button. 

4.5.  Press  Mode  button  (

⑤) 

for  more  than  10  seconds.  “CALIBRATING”  flashes. 

 

Calibration  will  be  finished  after  5-minutes  and  the  LCD  will  indicate 

 

“PASS”. If LCD indicates “FAIL”, repeat the calibration. 

 4.6. Press Enter (

②), 

and return to the User Mode

  

Summary of Contents for Falcon-II

Page 1: ...ay Delta BC V4G 1M3 Canada Phone 604 940 7007 Fax 604 940 7044 www yestek com REV A JUNE 2 2008 Falcon II Next Generation Air Quality Monitor CO2 Temperature OPERATION MANUAL Critical Environment Tech...

Page 2: ...2...

Page 3: ...IP FOR A PERIOD OF EIGHTEEN MONTHS INCLUDING CO2 SENSOR FROM THE DATE OF PURCHASE BY THE ORIGINAL OWNER IF THE PRODUCT SHOULD BECOME DEFECTIVE WITHIN THIS WARRANTY PERIOD WE WILL REPAIR OR REPLACE IT...

Page 4: ...LIABILITY REASONS CETCI HAS A POLICY OF PERFORMING ALL NEEDED REPAIRS TO RESTORE THE INSTRUMENT TO FULL OPERATING CONDITION PRIOR TO SHIPPING EQUIPMENT TO CETCI CONTACT OUR OFFICE FOR AN RMA RETURNED...

Page 5: ...S MANUAL ALL INFORMATION CONTAINED IN THIS MANUAL IS BELIEVED TO BE TRUE AND ACCURATE AT THE TIME OF PRINTING HOWEVER AS PART OF IT S CONTINUING EFFORTS TO IMPROVE IT S PRODUCTS AND THEIR DOCUMENTATIO...

Page 6: ...E 7 1 0 GENERAL 8 2 0 SPECIFICATIONS 8 9 3 0 DIMENSIONS 10 4 0 INSTRUMENT FEATURES 11 12 5 0 OPERATION 13 5 1 OPERATING MODES 13 5 2 DETAILED OPERATING INSTRUCTIONS 13 16 5 22 OPERATION MODE ADJUSTMEN...

Page 7: ...mory The instrument may be hand held or will easily stand on a flat surface The FALCON II instruments are manufactured to provide good value to the end user Calibration and repair is available at our...

Page 8: ...wall configuration only Power Requirement 160 mA Peak 15 mA average from 6V Outputs Normally Low 100mA max 24 VDC Adjustable set point factory setting is 1000ppm hysteresis is 50ppm One RJ 45 Connecto...

Page 9: ...er C or 2 ppm per C whichever is greater referenced to 25 C Pressure Dependence 0 13 of reading per mm Hg Corrected via user input for altitude Response Time 2min for 63 of step change Warm Up Time 60...

Page 10: ...10 3 0 DIMENSIONS 6 50 165mm 3 19 81 1mm 0 96 24 3mm...

Page 11: ...INSTRUMENT FEATURES FUNCTION PUSH BUTTONS MODE UP DOWN ENTER left to right ON OFF PUSH BUTTON LED INDICATOR LCD DISPLAY TEST GAS INLET OPENING FLIP DOWN STAND ALKALINE BATTERY ACCESS DOOR WALL ADAPTER...

Page 12: ...12 4 0 INSTRUMENT FEATURES CONT D Changing Alkaline Batteries...

Page 13: ...d ALARM Alarm when CO2 concen tration exceeds one threshold alarm Alarm level can be changed through the keypad menu The audible alarm can be switched on off through the keypad menu when the speaker i...

Page 14: ...go through the following sequence Temp C Temp F Vent Rate lps Vent Rate cfm p NOTE lps refers to Liter Per Second Per Person cfm p refers to Cubic Feet Per Minute Per Person 5 22 OPERATION MODE ADJUST...

Page 15: ...e Mode button until OUTSIDE flashes 3 2 Press Enter to show OUTSIDE CO2 and PPM flashes Press Up Down to adjust the reading 3 3 Press the Enter save the setting and return to the User Mode After modif...

Page 16: ...adings since the instrument was last switched on 6 1 Press the Mode button until MAX MIN flashes 6 2 Press Enter button MAX and MIN CO2 reading shows alternating 6 3 CLR will flash if press Up Down Pr...

Page 17: ...17...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...

Reviews: