background image

NOTES:

1. Full Load Amps (FLA) marked on motor nameplate.

2. Use minimum 14 AWG copper conductors for absorption chiller power supply.

Table 1 ELECTRICAL DATA

MODEL

WFC-SC10

WFC-SH10

WFC-SC20

WFC-SH20

WFC-SC30

WFC-SH30

POWER

SUPPLY

(V)

208

208

208

SOLUTION PUMP

(3 PH)

OUTPUT

FLA

(HP)

(A)

1/8

0.46

1/6

0.75

1/3

2.04

POWER SUPPLY

MIN. CIRCUIT AMPS

MAX. FUSE SIZE

)

A

(

)

A

(

5

1

6

.

0

5

1

9

.

0

5

1

6

.

2

20

POWER WIRING

Select  the  disconnect,  fuses  and  supply 

conductors  for  each  absorption  chiller  based  on

the minimum circuit ampacity and maximum fuse

size  on  the  UNIT  NAMEPLATE  as  per  the

Electrical  Data  in  Table  1. Install  conduit  to  the

field wiring junction box and leave sufficient clear-

ance  for  removal  of  panels  and  service  access.

DO NOT attach conduit to the absorption chiller

cabinet. The 1/2 in. trade size conduit entry in the 

junction box will accommodate four (3 live and 1

grounded)  14  AWG  copper  conductors  in  most

wire  styles. DO  NOT  USE  ALUMINUM 

CONDUCTORS.

Locate  the  disconnect  within  sight  of  and

readily accessible to the equipment, per Section

440-14 of the National Electrical Code.

DO  NOT  CLOSE  THE  DISCONNECT  until

approved  by  an  Authorized  Yazaki  Service

Provider.

CONTROL WIRING

All  field  control  wiring  connections  to  the

absorption chiller are low voltage (less than 30 V

AC) class 2 circuits and may be installed with or

without conduit. A 1/2 in. trade size conduit should

be  installed  to  protect  the  wire  against  physical

damage  or  for  aesthetic  reasons. If 

conduit is not used, a bushing must be inserted

into  the  wire  entries  of  the  junction  box. Route

additional  wiring  to  the  control  box  for  optional

input and output controls through the absorption

chiller junction box.

Motor contactors and overload relays for the

chilled/hot water pump, cooling water pump, heat

medium  pump  and  cooling  tower  fan  are  not

installed  in  the  absorption  chiller  and  must  be 

supplied  by  others. Refer  to  the  relevant  Field

Wiring  Diagram  (Single  Module  or  Multiple

Modules)  for  the  recommended  wiring  of  these

controls.

Use 18 AWG type T wire or equivalent for all

low  voltage  field  circuits  up  to  50  ft. (for  longer 

distances use a 16 AWG conductor).

Summary of Contents for Aroace WFC-SC10

Page 1: ...t medium hot water at 158o F to 203o F from a process cogeneration solar or other waste heat source CONTENTS INSTALLATION INSTRUCTIONS WFC SC10 20 30 WFC SH10 20 30 GENERAL Page STANDARD SPECIFICATION...

Page 2: ...c a p a C 2 This equipment should only be installed by trained and qualified personnel who are familiar with absorption chillers All precautions in these instructions on tags and labels attached to t...

Page 3: ...ms 6 Fuses 4 Installation Instructions 1 and Operating Instructions 1 MODEL DESIGNATION WFC Water Fired Single Effect Absorption Chiller Chiller Heater Model Selection SC Chiller SH Chiller Heater Coo...

Page 4: ...tion Box 19 1 4 TOP 3 5 Field Wiring Junction Box 31 5 4 9 26 4 29 9 33 1 26 4 4 Eye Bolts For Lifting Mounting Plate 7 5 38 2 LEFT FRONT REAR 0 8 74 8 9 0 6 1 12 5 16 4 Cooling Water Outlet 2 NPT Coo...

Page 5: ...tlet 2 1 2 NPT Cooling Water Absorber Inlet 2 1 2 NPT 3C Note Cooling Water Crossover Pipe Field Connections Shown In Are 3 Sweat Type L Copper 14 8 5 EQUIPMENT DIMENSIONS WFC SC30 SH30 All dimensions...

Page 6: ...TYPICAL SYSTEM DESIGN SINGLE MODULE WFC SC10 SH10 WFC SC20 SH20 WFC SC30 SH30 6...

Page 7: ...TYPICAL SYSTEM DESIGN MULTIPLE MODULES 2 X MODULES WFC SC20 SH20 WFC SC30 SH30 7...

Page 8: ...CN2 TMC1 CPU CPU CPU S3 EGBON HM CM CHD CHE S4 S5 S6 S7 S8 S11S12 S13 S14 S3 S4 S5 S6 S7 S8 S11S12 S13 S14 CP TB2 CN 16 LTPV CIRCUIT LTVP FE P2E P1E CIR HIR IRS LS AC24V DCP ST2 IF1 IF2 MGC2 4 OUC 5 T...

Page 9: ...ating status General fault alarm Additional interlock NC or NO Input control from temp switch 36 5 F ON 39 2 F OFF OPTIONAL CONTROL BOX CONNECTIONS TERMINAL DESCRIPTION REMARKS S1 S2 Heat medium suppl...

Page 10: ...POSITION DO NOT TIP OVER The dry weight and overall dimensions are shown in PHYSICAL DATA on Page 3 as a guide for rigging add 6 in to overall height for skid When moving the absorption chiller check...

Page 11: ...WFC SC30 SH30 FRONT WFC SC20 SH20 FRONT WFC SC20 SH20 A C FRONT WFC SC20 SH20 FRONT WFC SC10 SH10 D E F Mounting Plate Fig 3 INSTALLATION CLEARANCES IN 11 INSTALLATION AREA MODEL DIM IN No WFC A B 1...

Page 12: ...ing water crossover piping CHILLED HOT WATER PIPING The chilled hot water piping contains chilled water during cooling operation and hot water during heating operation and must be adjustment plates sh...

Page 13: ...pipe and interlock the switch with the absorption chiller controls refer to Optional Field Wiring Connections circuit should be filled with a glycol solution of adequate concentration to prevent freez...

Page 14: ...d 3 way valve CWV will bypass cooling water to the sump whenever the cooling water inlet temperature is below 65O F Wherever possible install the cooling tower at the same level or above the absorptio...

Page 15: ...on the left side of each unit Optional field wiring connections for accessories and alarms are provided in the should be drained from the chiller heater When the cooling water circuit is not drained...

Page 16: ...ONLY Option 3 HEAT INPUT CONTROL BY HEAT MEDIUM BYPASS VALVE ONLY OPTIONAL COOLING WATER TEMPERATURE CONTROL With Cooling Water Valve Override OPTIONAL COOLING WATER TEMPERATURE CONTROL Without Cooli...

Page 17: ...TDO for CWV STANDARD JUNCTION BOX CONNECTIONS TERMINAL DESCRIPTION REMARKS 3 P1D P1E Chilled hot water pump thermal overload 4 P2D P2E Cooling water pump thermal overload 5 FD FE Cooling tower fan th...

Page 18: ...ls the cooling water temperature by cycling the cooling tower fan 4 A Limit Switch 3VOP installed on the heat medium bypass valve closes when the valve is open 5 Optional controls override the Cooling...

Page 19: ...ONS TERMINAL DESCRIPTION REMARKS S1 S2 Heat medium RFH supply shutdown S9 S10 Auxiliary boiler BO 17 18 Input control EGON Heat available from temp switch 2 3 on CN Cooling Water flow Input control 11...

Page 20: ...nnect within sight of and readily accessible to the equipment per Section 440 14 of the National Electrical Code DO NOT CLOSE THE DISCONNECT until approved by an Authorized Yazaki Service Provider CON...

Page 21: ...t medium circuits may cause scal ing or corrosion if not correctly analyzed and maintained within the limits specified in Table 2 In some areas the water supply will contain minerals that cause scalin...

Page 22: ...OT operate the chiller 5 Power supply available near the chiller for a vacuum pump D CONTROL WIRING 1 Motor contactors and manual controls installed for all external motors 2 Control wiring 24V AC ins...

Page 23: ......

Page 24: ...STEMS INC 701 E PLANO PARKWAY SUITE 305 PLANO TEXAS 75074 6700 Phone 469 229 5443 Fax 469 229 5448 Email yazaki yazakienergy com Web www yazakienergy com This symbol on the product s nameplate means i...

Reviews: