Order no.
M13-CCF0000
Number of simultaneously utilizable inputs vertical configu-
ration
16
Input characteristic curve
IEC 61131-2, type 1
Initial data size
16 Bit
Technical data digital outputs
Number of outputs
12
Cable length, shielded
1000 m
Cable length, unshielded
600 m
Rated load voltage
DC 24 V
Reverse polarity protection of rated load voltage
ü
Current consumption from load voltage L+ (without load)
20 mA
Total current per group, horizontal configuration, 40°C
6 A
Total current per group, horizontal configuration, 60°C
6 A
Total current per group, vertical configuration
6 A
Output voltage signal "1" at min. current
L+ (-0.8 V)
Output voltage signal "1" at max. current
L+ (-0.8 V)
Output current at signal "1", rated value
0.5 A
Signal logic output
Sinking output
Output current, permitted range to 40°C
5 mA to 0.6 A
Output current, permitted range to 60°C
5 mA to 0.6 A
Output current at signal "0" max. (residual current)
0.5 mA
Output delay of "0" to "1"
2 µs / 30 µs
Output delay of "1" to "0"
3 µs / 175 µs
Minimum load current
-
Lamp load
10 W
Parallel switching of outputs for redundant control of a load not possible
Parallel switching of outputs for increased power
not possible
Actuation of digital input
ü
Switching frequency with resistive load
max. 1000 Hz
Switching frequency with inductive load
max. 0.5 Hz
Switching frequency on lamp load
max. 10 Hz
Internal limitation of inductive shut-off voltage
L+ (-45 V)
Short-circuit protection of output
yes, electronic
Trigger level
1 A
Number of operating cycle of relay outputs
-
Switching capacity of contacts
-
VIPA System MICRO
Hardware description
Technical data > Technical data CPU
HB400 | CPU | M13-CCF0000 | en | 18-50
52