X5
Function
Type
LED
green
Description
1
-
-
reserved
2
-
-
reserved
3
DI 1.0
I
Digital input DI 8
4
DI 1.1
I
Digital input DI 9 / Counter 3 (A) *
5
DI 1.2
I
Digital input DI 10 / Counter 3 (B) / Frequency 3 *
6
DI 1.3
I
Digital input DI 11 / Gate 3 *
7
DI 1.4
I
Digital input DI 12
8
DI 1.5
I
Digital input DI 13
9
DI 1.6
I
Digital input DI 14
10
DI 1.7
I
Digital input DI 15 / Latch 3 *
*) Max. input frequency 100kHz otherwise 1kHz.
5.4.3 Parametrization
5.4.3.1
Adress assignment
Sub module
Input
address
Access
Description
DI24/DO16
136
BYTE
Digital input I+0.0 ... I+0.7 (X1)
137
BYTE
Digital input I+1.0 ... I+1.7 (X5)
5.4.3.2
Hardware interrupt
With the parameter
‘Hardware interrupt at ...’
you can specify a hardware interrupt for
each input for the corresponding edge. The hardware interrupt is disabled, if nothing is
selected (default setting). A diagnostics interrupt is only supported with
Hardware inter-
rupt lost
. Select with the arrow keys the input and enable the according hardware inter-
rupts.
Here is valid:
n
Rising edge: Edge 0-1
n
Falling edge: Edge 1-0
X5: DI byte 1
Parameter hardware con-
figuration
VIPA System MICRO
Deployment I/O periphery
Digital input > Parametrization
HB400 | CPU | M13-CCF0000 | en | 18-50