1
Number of pulses
2
Period duration
3
Pulse duration
4
Pulse pause
Parameter overview
Operating parameters
Description
Assignment
Output format
Here specify the range of values for the output. The CPU
hereby determines the pulse duration:
n
Per mil
–
Output value is within 0 ... 1000
–
Pulse duration = (Output value / 1000) x Period
n
S7 Analog value:
–
Output value is Siemens S7 analog value 0 ...
27648
–
Pulse duration = (Output value / 27648) x Period
Per mil
Time base
Here you can set the time base, which will apply for resolu-
tion and range of values of the period duration, minimum
pulse duration and on-delay.
n
1ms: The time base is 1ms
n
0.1ms: The time base is 0.1ms
n
1µs: The time base is 1µs
0.1ms
On-delay
This parameter is ignored.
0
VIPA System MICRO
Configuration with VIPA SPEED7 Studio
Deployment I/O periphery > Pulse train
HB400 | CPU | M13-CCF0000 | en | 18-50