4.5 Application Presets
118
YASKAWA ELECTRIC
TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
Table 4.18 Parameters Automatically Saved as Preferred (A2-01 to A2-16)
Note:
A sequence to release the brake is needed when the multi-function output photocoupler P2-PC
closes.
Hoist Application Preset Specifics on page 118
for more information.
■
Hoist Application Preset Specifics
This section lists some important points when using the Hoist Application Preset (A1-06 =
6).
Conditions for Opening and Closing the Holding Brake
Use an output signal as described below to operate the holding brake in a hoist application.
Make sure that frequency detection is set so that it does not operate during baseblock (L4-07
= “0”). Even when an external baseblock command is present, the output frequency will rise
when a run command is entered. If frequency detection were to be enabled during baseblock,
(i.e., L4-07 = 1) then the brake would be improperly released. To activate and release the
brake using the multi-function output terminals P2-PC, program the drive as shown in the
table below:
d1-01 Frequency
Reference 1
6.0 Hz
d1-02 Frequency
Reference 2
30.0 Hz
d1-03 Frequency
Reference 3
60.0 Hz
H1-05
Multi-Function Digital Input Terminal S5 Function
3: Multi-Step Speed 1
H1-06
Multi-Function Digital Input Terminal S6 Function
4: Multi-Step Speed 2
H2-02
Terminals P1 Function Selection (open-collector)
37: During frequency output
L3-04
Stall Prevention Selection during Decel
0: Disabled
L8-05
Input Phase Loss Protection Selection
1: Enabled
L8-07
Output Phase Loss Protection
1: Triggered when a single phase is lost
L8-38
Carrier Frequency Reduction
1: Always derated
L8-41
Current Alarm Selection
1: Enabled (alarm output)
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection
d1-03
Frequency Reference 3
C1-01
Acceleration Time 1
E2-01
Motor Rated Current
C1-02 Deceleration
Time
1 H1-05
Multi-Function Digital Input Terminal
S5 Function
C6-02
Carrier Frequency Selection
H1-06
Multi-Function Digital Input Terminal
S6 Function
d1-01
Frequency Reference 1
H2-01
Terminals MA, MB, and MC Function
Selection
d1-02
Frequency Reference 2
L1-01
Motor Overload Protection Selection
No.
Parameter Name
Optimum Setting