Perform Mechanical Installation
2
STEP
2.1 Verify installation environment.
Mechanical installation and mounting footprint vary by model. Refer to the U1000
iQpump Drive User Manual No.
TOEPYAIUPW01, Chapter 2: Mechanical Installation for details. Ensure the installation conditions are suitable to prolong and
optimize performance life.
Environment
Conditions
Installation Area
Indoors
Ambient Temperature
IP00/Open Type enclosure: -10 °C to +50 °C (14 °F to 122 °F)
IP20/NEMA 1, UL Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F) <1>
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that
the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
Humidity
95% RH or less and free of condensation
Storage Temperature -20 °C to +60 °C (-4 °F to +104 °F)
Surrounding Area
Install the drive in an area free from:
•
oil mist and dust
•
metal shavings, oil, water, or other foreign materials
•
radioactive materials
•
combustible materials (e.g., wood)
•
harmful gases and liquids
•
excessive vibration
•
chlorides
•
direct sunlight.
Altitude
1000 m (3281 ft.) or lower, up to 3000 m (9843 ft.) with derating
Vibration
20 to 55 Hz: 5.9 m/s
2
(2
0104 to 2
0248, 4
0096 to 4
0414: 2.0 m/s
2
)
Orientation
Install the unit vertically to maintain maximum cooling effects.
<1> Attach a top protective cover and bottom cover from the optional End Cap Kit to an IP00/Open Type enclosure drive to convert the
drive to an IP20/NEMA 1, UL Type 1 enclosure drive.
2.2 Maintain installation clearances.
A
C
A B
B
D
E
Side Clearance
Top/Bottom Clearance
Install Type
Minimum Spacing
E
A
B
C
D
50 mm (1.97 in)
30 mm (1.18 in)
200 mm (7.87 in)
120 mm (4.72 in)
Airflow direction
Ensure the back panel is placed against a closed flat surface
for proper cooling.
NOTICE:
Abnormal Operation. Avoid placing peripheral
devices, transformers, or other electronics near the drive as
the noise created can lead to abnormal operation. Take proper
steps to shield the drive from electrical interference if such
devices must be used in close proximity to the drive.
NOTICE:
Equipment Damage. Prevent foreign matter such as
metal shavings and wire clippings from falling into the drive
during installation. Failure to comply could result in damage
to the drive. Place a temporary cover over the top of the drive
during installation. Remove the temporary cover before drive
start-up, as the cover will reduce ventilation and cause the
drive to overheat.