YASKAWA TOEPYAIUPW02A U1000 iQpump Drive Quick Start Procedure
U1000 iQpump Drive
Quick Start Procedure
Page 20
of 25
Hand Mode Operation
11
STEP
11.1 HAND Mode
Perform these tasks to operate the drive in HAND mode:
•
Program all parameters
•
Verify motor rotation direction
HOA Keypad
Press to access HAND Speed. Use to change HAND Speed value.
Adjust Hand Speed from Analog Input (0 – 10 V)
+
0 – 10 V Connection
0 ~ 10 Vdc
+V AC A1 A2 A3 FM AM AC RP AC 24V
Cable
Shield
E(G)
Set parameter P5-01 (HAND Mode Ref.) to 0 to adjust the hand mode reference from an external 0 – 10 V signal
connected to terminals AC and A3.
Press to save value.
P5-02= 0040.0
Hz
Hand Reference 1
-MONITR- PRG
(0.0~60.0)
FWD
HOME
"40.0Hz"
U1-02= 40.00Hz
U1-01= 40.00
HZ
- MODE - DRV Rdy
U1-91= 34.2PSI
MONITOR
LSEQ
LREF
Hand Reference 1
Press HAND mode
Press to turn OFF