AUTO Mode Operation (continued)
10
STEP
10.2 Set System Setpoint (continued)
10.2 Set System Setpoint
Press AUTO key to
start the drive.
U1-02= 0.00Hz
U5-99= 0.0
PSI
Auto Setpoint
- MODE - DRV Rdy
U1-91= 56.2PSI
MONITOR
LSEQ
LREF
The drive starts in AUTO mode when the feedback signal falls below
the programmed level in parameter P1-04 for the time specified in P1-05.
Start Pump System
Start
Delay
145
Start/Draw Down
Level P1-04
System Setpoint
(Example 80 PSI)
Feedback signal from
pressure transducer
(4 – 20 mA)
0
Pressur
e
Start Level Delay (P1-05)
(Example 5.0 seconds)
WAIT
Refer to Figure 8.2, Start/Draw Down Level.