TOEP C730600 89B PROFINET Installation Manual
Fault Condition
Fault
Declared
Status
Value
(U6-98/
U6-99)
Description
No Station Name
None
1305
No Station Name has been programmed into the option.
Bad Station Name
Programmed
None
1306
Station Name Programmed is invalid and must be
reprogrammed.
Init. Failure
None
1307
Initialize error on power-up.
Permanent
Communication Loss
bUS
1308
Fatal error in MAC/PHY hardware Cycle power.
Bad IP
Configuration
None
1309
Invalid IP/subnet/gateway address programmed into
F7-01
-
F7-12
.
Two drive monitor parameters,
U6-98
and
U6-99
assist in network troubleshooting:
•
U6-98
: Shows the first declared fault since the last power cycle. Only cleared upon
drive power-up.
•
U6-99
: Shows the present option SI-EP3 status. Cleared upon a network-issued fault
reset and upon power-up.
If another fault occurs while the original fault is still active, parameter
U6-98
retains the
original fault value and
U6-99
stores the new fault status value.
◆
Option Compatibility
You can connect a maximum of 3 options at the same time depending on the type of
option.
Note:
•
You can only connect one option to the GA500 and HV600 drives. Connect the option to the CN5 connector.
•
You can connect two options to an FP605 drive. Connect the communication option to the CN5-A connector.
•
Compatible communication options are different for different models. Refer to the drive manuals for more
information.
Table 9.2 Option Compatibility
Option
Connector
Number of Options
Possible
PG-B3
, PG-X3
CN5-B, C
2
PG-RT3
, PG-F3
CN5-C
1