Email Settings
The
“
Email Server IP Address
”
text box must contain the IP address of the email server.
The subnet address is configured in drive parameters
F7-05
through
F7-08
. The
configured email alerts will use the server at this address when sending emails.
Enter the email server port in the
“
Email Server Port
”
text box.
The value in the
“
From Email Address
”
text box identifies the origin of the email alerts to
the recipient.
To save the entered information into the option, click
“
Save Email Settings
”
.
9
Troubleshooting
◆
Drive-Side Error Codes
Drive-side error codes appear on the drive keypad.
lists causes of the
errors and possible corrective actions. Refer to the drive Technical Manual for additional
error codes that may appear on the drive keypad.
■
Faults
Both
bUS [Option Communication Error]
and
EF0 [Option Card External Fault]
can
appear as a fault. When a fault occurs, the keypad ALM LED stays lit. When an alarm
occurs, the ALM LED flashes. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide
to help remedy the fault:
•
Is the communication line properly connected to the option? Is it loose?
•
Did you correctly connect the communication line to the option?
•
Is the PLC program working? Is the controller/PLC CPU stopped?
•
Did a momentary power loss interrupt communications?
Code
Name
Causes
Possible Solutions
bUS
Option
Communication Error
The drive did not receive a
signal from the controller.
The communications cable
wiring is incorrect.
•
Check for wiring errors.
•
Correct the wiring.
An existing short circuit or
communications disconnection
Check disconnected cables and short
circuits and repair as needed