22
YASKAWA
TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
6 Procedure A
6
Procedure A
Use
Procedure A
steps to install the option on drives with
IP00/IP20 Open Chassis &
IP20/NEMA Type 1
enclosures or enclosure type digits A, B or F within the model number.
◆
Procedure A Steps
DANGER!
Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to
comply will result in death or serious injury. Before installing the option, disconnect all power to the drive.
The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED
will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes
after all indicators are off and measure the DC bus voltage level to confirm safe level.
NOTICE:
Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling
the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.
1.
Shut off power to the drive, wait at least five minutes after confirming the DC bus
voltage is safe, then loosen the screw that fastens the front cover in place and
remove the front cover. This drive front cover will be replaced by the option cover.
Cover removal varies depending on drive size.
Figure 7
Figure 7 Remove the Front Cover
2.
The remaining installation steps differ by drive model. Find the drive model number
and identify the Enclosure Type Digit on the drive nameplate and refer to the
appropriate
row and “
Proceed to STEP
” column.
Table 7 Procedure A- Steps by Drive Model
Enclosure Type Digit within
Model Number
Enclosure Type
Drive Model
Proceed to STEP
A, B
IP20/Open-Chassis
CIMR-V
A
B
STEP
F
IP20/NEMA Type 1
<1> Installing the option on an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while maintaining
IP20 conformity.
CIMR-V
A
F
STEP