12 Fault Diagnosis and Possible Solutions
YASKAWA EUROPE GMBH
YEU SIEP C710616 86A - AC Drive A1000 Option Powerlink - Technical Manual
37
SDO Abort Codes
SDO abort codes are supported as specified in DS301. Additionally the abort codes listed below are implemented.
Table 16 SDO Abort Codes
Drive-Side Error Codes
Drive-side error codes appear on the drive’s digital operator. Causes of the errors and corrective actions are listed in
. For
additional error codes, refer to the technical manual for the drive.
The bUS (Powerlink
Option Communication Error) and EF0 (External Fault Input from the Powerlink
Option) may appear as an alarm or a fault. If
they occur as an alarm, the “ALM” LED on the drive digital operator will blink and the alarm code will flash in the display. When these occur as a
fault, the “ALM” LED will light and the display will show the fault code.
If communication stops while the drive is running, check the following items:
• Is the Powerlink
Option properly installed?
• Is the communication line properly connected to the Powerlink
Option? Is it loose?
• Is the controller program working? Has the controller CPU stopped?
• Did a momentary power loss interrupt communications?
Faults
lists possible faults when using a communication option. The drive’s fault contact will close if one of these faults occur.
Table 17 Fault Display and Possible Solutions
FF0E
External fault at input terminal S2
EF2
0x43
FF44
Mechanical weakening detection 1
oL5
0x44
FF45
Mechanical weakening detection 2
UL5
0x45
FF46
Current offset fault
CoF
0x46
FF47
Programming Error 1
PE1
0x47
FF49
Current offset fault
dWFL
0x49
6301
Error during object content selection
-
-
SDO Abort Code
Description
0602 0010 (Hex)
Consecutive MEMOBUS/Modbus Read/Write/Enter commands are sent but the wait time between messages is too short.
A MEMOBUS/Modbus Read or Write Response (2140 (Hex) and 2150 (Hex)) was attempted but no or an incorrect
MEMOBUS/Modbus address has been written to object 2040 (Hex) or 2050 (Hex) before.
A MEMOBUS/Modbus write request has been sent during DC bus under voltage.
0602 0022 (Hex)
Drive Profile DSP402 is used and a value is written to object 6042 (Hex) (vl Target Velocity) while the drive status is not
“Operation Enable”.
Object 2155 (Hex) is tried to be read while the SI-EL3 option is not in “Operational” state.
A MEMOBUS/Modbus Read or Write command (2040 (Hex) and 2050 (Hex)) was performed with an invalid MEMOBUS/
Modbus address.
Digital Operator Display
Fault Name
bUS
Powerlink
Option Communication Error
After establishing initial communication, the connection was lost.
Only detected when the run command or frequency reference is assigned to the option (b1-01=3 or b1-02=3).
Cause
Possible Solution
Master controller (PLC) has stopped communicating.
Check for faulty wiring.
Correct any wiring problems.
Communication cable is not connected properly.
A data error occurred due to noise.
Check the various options available to minimize the effects of noise.
Take steps to counteract noise in the control circuit wiring, main circuit lines, and ground wiring.
If a magnetic contactor is identified as a source of noise, install a surge absorber to the contactor coil.
Make sure the cable used fulfills the Powerlink
requirements. Ground the shield on the controller side and on the Powerlink
Option side.
Powerlink
Option is damaged.
If there are no problems with the wiring and the error continues to occur, replace the Powerlink
Option.
A Powerlink state transition from OP
PRE_OP_1 was made
when the drive was in OPERATION enabled.
Check and correct state machine transitions in control word.
Digital Operator Display
Fault Name
EF0
External Fault Input from Powerlink Option
The alarm function for an external device has been triggered.
Cause
Possible Solution
An external fault is being sent from the upper controller (PLC).
Remove the cause of the external fault.
Reset the external fault input from the upper controller (PLC) device.
Problem with the upper controller (PLC) program.
Check the program used by the upper controller (PLC) and make the appropriate corrections.