(1) CtrMode
:
Set the control mode of reactive power
0: Disable dispatch mode
1: Remote dispatch mode
2: Local control, by Q
3: Local control, by PF
4: PF(P) curve
5: Q(U) curve
(2) PF Set
:
Set the PF value
NOTE
: You can change the reactive power by adjusting the power factor
(3) PF(P) Curve
:
PF curve mode
NOTE:
The power factor changes according to the power change, as shown in Figure
4-16:
Figure 4-16 PF(P) Curve Mode
(4) Q(U) Curve
:
Q(U) curve mode
Note: The reactive compensation changes according to the grid voltage change, as
shown in Figure 4.17.
Capacitive
PF
-1
1
Inductive
(PFCurveP1,PFCurvePF1)
(PFCurveP2,PFCurvePF2)
(P%)
INSTRUCTION:
The PF (P) Curve function is only available for IEEE-1547 grid standard.
INSTRUCTION:
The Q(U) curve function is only available for IEEE-1547 grid standards.