EN-10
Installation Orientation
Install the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter, always pro-
vide the following installation space to allow normal heat dissipation.
Exterior and Mounting Dimensions
Open Chassis Inverters (IP00)
Enclosed Wall-mounted Inverters [IEC IP20, NEMA1(Type1)]
IMPORTANT
1. The same space is required horizontally and vertically for IP00, IP20 and NEMA 1 Inverters.
2. Always remove the top protection cover after installing an Inverter with an output of 18.5 kW or less in a
panel.
Always provide enough space for suspension eye bolts and the main circuit lines when installing an
Inverter with an output of 22 kW or more in a panel.
A
50 mm min.
30 mm min.
30 mm min.
B
120 mm min.
Air
Air
Vertical Space
Horizontal Space
A
B
50 mm
120 mm
W
W1
3
H1
H2
D
H
D1
4-d
t1
W
W1
4-d
H2
(5)
D1
D
H1
H
t1
(5)*
(5)*
* (10) for 200 V Class Inverters of 37 to 55 kW.
200V/400V Class Inverters of 0,4 to 18,5kW
200V Class Inverters of 22 to 55kW
400V Class Inverters of 22 to 55kW
W
W1
3
H1
H2
D
H0
D1
H3
4
H
4-d
t1
W
W1
H3
H0
H1
H2
D1
D
(5)
4-d
t1
(5)*
(5)*
H
Grommet
Max.10
* (7.5) for 200 V Class Inverters of 37 to 55 kW.
200V/400V Class Inverters of 0,4 to 18,5kW
200V Class Inverters of 22 to 55kW
400V Class Inverters of 22 to 55kW