The following simultaneous contradictory
settings:
• H3-02, H3-10, or H3-06 = B (PID Feedback)
while H6-01
(Pulse Train Input) = 1 (PID Feedback)
• H3-02, H3-10, or H3-06 = C (PID Target Value)
while H6-01 = 2
(pulse train input sets the PID target value)
• H3-02, H3-10, or H3-06 = C (PID Target Value)
while b5-18 = 1
(enables b5-19 as the target PID value)
• H6-01 = 2 (PID target) while b5-18 = 1
(enables b5-19 as the target PID value)
Disable one of the PID selections.
HOA Keypad Display
Error Name
oPE09
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1 to 4).
Cause
Possible Solutions
The following simultaneous contradictory settings
have occurred:
• b5-15 is not set to 0.0 (PID Sleep Function
Operation Level)
• The stopping method is set to either DC
Injection Braking or coast to stop with a timer
(b1-03 = 2 or 3).
• Set b5-15 to a value other than 0.0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
b5-01 is set to 1 or 2, enabling PID control, but the
lower limit for the frequency reference (d2-02) is
not set to 0 while reverse output is enabled (b5-11
= 1).
Correct the parameter settings.
b5-01 is set to 3 or 4, enabling PID control, but the
lower limit for the frequency reference (d2-01) is
not 0.
Correct the parameter settings.
HOA Keypad Display
Error Name
oPE10
V/f Data Setting Error
One of the following setting errors has occurred:
E1-09
≤
E1-07 < E1-06
≤
E1-11
≤
E1-04
Cause
Possible Solutions
V/f pattern setting error.
Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.
HOA Keypad Display
Error Name
oPE11
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Cause
Possible Solutions
The following simultaneous contradictory settings
have occurred: C6-05 > 6 and C6-04 > C6-03
(carrier frequency lower limit is greater than the
upper limit).
If C6-05
≤
6, the drive operates at C6-03.
Correct the parameter settings.
The upper and lower limits between C6-02 and
C6-05 are contradictory.
HOA Keypad Display
Error Name
oPE28
Sequence Timer Error
One or more of the sequence timers is not set in the correct order.
Cause
Possible Solutions
One of the following contradictory settings is true:
• S2-01 > S2-02
• S2-06 > S2-07
• S2-11 > S2-12
• S2-16 > S2-17
Correct the parameter settings.
5.4 Operator Programming Errors
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
205
5
Troubleshooting