4.4 Pump Application Presets
The following sections list the parameters affected by the different Application Presets.
Note:
Setting A1-03 to 6011 (VTC Pressure Control) changes the Quick Start and Pre-set parameters (tables below) and also changes HAND
Mode so that it is no longer lower-limited by the minimum pump frequency or the thrust frequency. Also, the default for P1-06 when in
RPM mode is 1800 RPM instead of 2400 RPM.
u
Parameters Set Depending on A1-03 Setting
The following table shows the parameters that are set depending on the A1-03 initialization:
A1-03 = 6008
(A1-06 = 8)
Pressure Control
A1-03 = 6009
(A1-06 = 9)
Pump Down Level
A1-03 = 6010
(A1-06 = 10)
Geothermal Mode
A1-03 = 6011
(A1-06 = 11)
VTC Pressure Ctl
A1-03 = 7770
(A1-06 = 1)
General Purpose
Parameter
Value
Parameter
Value
Parameter
Value
Parameter
Value
Parameter
Value
b5-09
1
b1-01
5
b5-03
5.0
b1-01
1
b5-39
2
b5-01
0
C1-01
15.0 sec
b1-02
1
P1-02
6
H3-10
21
C1-02
15.0 sec
b5-01
0
P2-01
2
o1-08
180
E2-04
4
C1-01
25.0 sec
P2-23
0.00%
L5-01
0
C1-02
25.0 sec
P1-03
100.0 PSI
H1-06
4
P1-06
35.0 Hz
H1-07
F
P2-03
15sec
H2-01
0
P2-23
0.00%
H2-02
A
P3-50
35.0 Hz
H3-10
2
P3-60
35.0 Hz
L5-01
0
P3-70
35.0 Hz
L5-04
180.0 sec
P4-12
0.0 Hz
o1-06
0
P5-02
6.0 Hz
P1-05
0 sec
Q5-03
40.0 PSI
P1-06
0.0 Hz
Q5-06
50.0 PSI
P4-12
0.0 Hz
Q5-09
20.0 PSI
P4-17
0.0 min
Q5-10
5.0 min
P5-02
0.0 Hz
Q5-11
2
Q5-16
1.00
Q5-17
3.0 sec
H2-01
80H
H2-02
81H
H2-03
82H
4.4 Pump Application Presets
118
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide