11 Drive Control and Programming
YASKAWA
TOEPC71061732E HV600 Drive Installation & Primary Operation
67
Table 11.1 Auto-Tuning Mode Selection
Type
T1-01
Application Conditions and Benefits
A1-02 = 0
[Control Method
Selection = V/f]
Rotational Auto-Tuning
0
Recommended tuning mode for the most accurate results. Select this tuning mode when:
•
You can decouple the motor from the load.
•
You cannot decouple the motor from the load, but the motor load is less than 30%.
Yes
Stationary Line-Line Resistance
2
Select this tuning mode when:
•
The drive and motor capacities are different.
•
The drive is in V/f Control.
•
You have replaced the drive and motor.
Yes
Table 11.2 EZ Tuning Mode Selection
Type
T4-01
Application Conditions and Benefits
A1-02 = 8
[EZOLV]
Motor Parameter Setting
0
Set the motor parameters.
Yes
Line-to-Line Resistance
1
Select this tuning mode after you replace the drive, motor, and motor cables.
Yes
◆
Drive Parameters
Icon
Description
The parameter is available when operating the drive with V/f Control.
The parameter is available when operating the drive with Open Loop Vector Control for PM.
The parameter is available when operating the drive with EZ Open Loop Vector Control.
RUN
The parameter can be changed settings during run.
Note:
Gray icons identify parameters that are not available in the specified control method.
Refer to the following table when setting the most important parameters.
No.
(Hex.)
Name
Description
A1-00
(0100)
RUN
Language Selection
Sets the language for the HOA keypad.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
A1-02
(0102)
Control Method Selection
Sets the control method for the drive application and the motor.
0 : V/f Control
5 : PM Open Loop Vector
8 : EZ Vector Control
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
3330 : 3-Wire Initialization
3410 : HVAC Initialization
b1-01
(0180)
Frequency Reference Selection 1
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Serial Communications
3 : Option PCB
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV