YASKAWA
TOEPC71061732E HV600 Drive Installation & Primary Operation
13
Item
Specification
Overload Protection
Drive stops when the output current is more than these overload tolerances:
•
110% of the rated output current for 60 seconds
•
140% of the rated output current for 2.5 seconds when the drive output frequency is 3 Hz
The permitted frequency of overload is one time each 10 minutes.
Note:
If output frequency < 6 Hz, the drive can trigger the overload protection function when the output current is in the overload tolerance range.
Overvoltage
Protection
208 V class: Stops when the DC bus voltage is more than approximately 410 V
480 V class: Stops when the DC bus voltage is more than approximately 820 V
Undervoltage
Protection
208 V class: Stops when the DC bus voltage decreases to less than approximately 190 V
480 V class:
•
Stops when the DC bus voltage decreases to less than approximately 350 V when you use an input voltage less than 400 V
•
Stops when the DC bus voltage decreases to less than approximately 380 V when you use an input voltage less than 460 V
•
Stops when the DC bus voltage decreases to less than approximately 440 V when you use an input voltage of 460 V or more
Momentary Power
Loss Ride-thru
Immediately stops when power loss is 15 ms or longer.
Continues operation if power loss is shorter than 2 s (depending on parameter settings).
Note:
Stop time may be shortened depending on the load and motor speed.
Heatsink Overheat
Protection
The drive stops when the thermistor detects an IGBT temperature more than approximately 100 °C (212 °F). The trip temperature level is different for different
drive models.
Stall Prevention
Stall prevention is available during acceleration, deceleration, and during run.
Ground Fault
Protection
Electronic circuit protection
Note:
This protection detects ground faults during run. The drive will not provide protection when:
•
There is a low-resistance ground fault for the motor cable or terminal block
•
Energizing the drive when there is a ground fault.
DC Bus Charge LED
Charge LED illuminates when DC bus voltage is more than 50 V.
Table 5.3 Environment
Item
Specification
Area of Use
Indoors
Power Supply
Overvoltage Category III
Ambient Temperature
Setting
IP20/UL Type 1 and IP55/UL Type 12: -10 °C to +40 °C (14 °F to 104 °F)
IP20/UL Open Type: -10°C to +50 °C (14 °F to 122 °F)
•
When you install the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
•
Do not let the drive freeze.
•
You can use IP20/UL Open Type and IP20/UL Type 1 drives at a maximum of 60 °C (140 °F) when you derate the output current.
•
You can use IP55/UL Type 12 drives at a maximum of 50 °C (122 °F) when you derate the output current.
Humidity
95% RH or less
Do not let condensation form on the drive.
Storage Temperature
-20 °C to +70 °C (-40 °F to +158 °F) (short-term temperature during transportation)
Surrounding Area
Pollution degree 2 or less
Install the drive in an area without:
•
Oil mist, corrosive or flammable gas, or dust
•
Metal powder, oil, water, or other unwanted materials
•
Radioactive materials or flammable materials, including wood
•
Harmful gas or fluids
•
Salt
•
Direct sunlight
Altitude
1000 m (3281 ft) maximum
Note:
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 m to 4000 m (3281 ft to 13123 ft).
It is not necessary to derate the rated voltage in these conditions:
•
When you install the drive at 2000 m (6562 ft) or lower
•
When you install the drive between 2000 m to 4000 m (6562 ft to 13123 ft) and ground the neutral point on the power supply.
Vibration
•
10 Hz to 20 Hz: 1 G (9.8 m/s
2
, 32.15 ft/s
2
)
•
20 Hz to 55 Hz:
2011 to 2031, 4005 to 4034: 0.6 G (5.9 m/s
2
, 19.36 ft/s
2
)
2046 to 2273, 4040 to 4302: 0.2 G (1.96 m/s
2
, 6.43 ft/s
2
)
Installation
Orientation
Install the drive vertically for sufficient airflow to cool the drive.