TOEPC7106171GA FP605 Drive Installation & Primary Operation
75
Note:
• Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
• The maximum wiring length between the drive and motor is 100 m (328 ft). Keep the wire as short as possible.
• Keep the grounding wire as short as possible.
4.
Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications and local safety standards.
A - Braided shield cable
B - Metal plate
C - Cable clamp (conductive)
Figure 14.4 Ground the shield