74
YASKAWA
TOEPC7106171GA FP605 Drive Installation & Primary Operation
Drive Model
GFCI Model
Manufacturer: Mitsubishi Electric
Rated Current
A
Rated Leakage Current
mA
2059
NV125-SV
125
500
2075
NV250-SV
150
500
2088
NV250-SV
175
500
2114
NV250-SV
225
500
Table 14.5 Factory-Recommended GFCI (480 V Class)
Drive Model
GFCI Model
Manufacturer: Mitsubishi Electric
Rated Current
A
Rated Leakage Current
mA
4005
NV32-SV
15
500
4008
NV32-SV
15
500
4011
NV32-SV
20
500
4014
NV32-SV
30
500
4021
NV63-SV
50
500
4027
NV63-SV
63
500
4034
NV63-SV
63
500
4040
NV125-SV
100
500
4052
NV125-SV
125
500
4065
NV125-SV
125
500
4077
NV250-SV
150
500
4096
NV250-SV
200
500
◆
EMC Directive
Drives with built-in EMC filters were tested in accordance with European standard IEC/EN 61800-3, and comply
with the EMC Directive.
■
Install a Drive to Conform to the EMC Directive
Use this procedure to install drives that comply with the EMC Directive when the drive is a single unit or installed in
a larger device.
1.
Install the drive on a grounded metal plate.
2.
Wire the drive and motor.
3.
Ground the wire shielding on the drive side and motor side.
A - Drive
B - 100 m (328 ft) maximum
C - Motor
D - Metal conduit
E - Grounding wire
Figure 14.3 Wiring the Drive and Motor