62
YASKAWA
TOEPC7106171GA FP605 Drive Installation & Primary Operation
Refer to
to select ferrules and crimp terminals as specified by drive model and wire gauge.
Note:
To comply with UL standards, use UL Listed vinylcoated insulated copper wires for operation with a continuous maximum permitted
temperature of 75 °C at 600 V.
Table 13.1 Ferrules and Closed-Loop Crimp Terminals
Model
Recommended
Gauge
AWG, kcmil
Ferrule
Crimp Terminal Part Number
Manufacturer: PANDUIT Corp.
Type LCA
Type P
Type S
2011
R/L1, S/L2, T/L3
14
F80-10
N/A
N/A
N/A
U/T1, V/T2, W/T3
14
F80-10
N/A
N/A
N/A
12
N/A
LCA10-14-L
P10-14R-L
N/A
2017
R/L1, S/L2, T/L3
12
F81-10
N/A
N/A
N/A
U/T1, V/T2, W/T3
10
F82-10
N/A
N/A
N/A
10
N/A
LCA10-14-L
P10-14R-L
N/A
2024
R/L1, S/L2, T/L3
10
F82-15
N/A
N/A
N/A
U/T1, V/T2, W/T3
8
F83-12
N/A
N/A
N/A
10
N/A
LCA10-14-L
P10-14R-L
N/A
2031
R/L1, S/L2, T/L3
8
F83-15
N/A
N/A
N/A
U/T1, V/T2, W/T3
8
F83-12
N/A
N/A
N/A
10
N/A
LCA10-14-L
P10-14R-L
N/A
2046
R/L1, S/L2, T/L3
8
F83-18
N/A
N/A
N/A
U/T1, V/T2, W/T3
6
F84-18
N/A
N/A
N/A
8
N/A
LCA8-14-L
P8-14R-Q
S8-14R-Q
2059
R/L1, S/L2, T/L3
4
F85-18
N/A
N/A
N/A
U/T1, V/T2, W/T3
4
F85-18
N/A
N/A
N/A
6
N/A
LCA6-14-L
P6-14R-E
S6-14R-E
2075
R/L1, S/L2, T/L3
4
N/A
LCA4-56-L
P4-56R-E
S4-56R-E
U/T1, V/T2, W/T3
3 or 2
N/A
LCA4-56-L
or
LCA2-56-Q
S2-56R-X
6
N/A
LCA6-56-L
P6-56R-E
S6-56R-E
2088
R/L1, S/L2, T/L3
3 or 2
N/A
LCA4-56-L
or
LCA2-56-Q
S2-56R-X
U/T1, V/T2, W/T3
2
N/A
LCA2-56-Q
P2-56R-X
S2-56R-X
6
N/A
LCA6-56-L
P6-56R-E
S6-56R-E
2114
R/L1, S/L2, T/L3
1/0
N/A
LCA1/0-56-X
N/A
S1/0-56R-X
U/T1, V/T2, W/T3
1/0
N/A
LCA1/0-56-X
N/A
S1/0-56R-X
6
N/A
LCA6-56-L
P6-56R-E
S6-56R-E
4005
R/L1, S/L2, T/L3
14
F80-10
N/A
N/A
N/A
U/T1, V/T2, W/T3
14
F80-10
N/A
N/A
N/A
14
N/A
LCA10-14-L
P10-14R-L
N/A