B.3 Parameter Table
B
YASKAWA ELECTRIC
SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
365
■
b8: Energy Saving
b5-39
(1FFH)
PI Setpoint Display Digits
0: No decimal places
1: One decimal places
2: Two decimal places
3: Three decimal places
Default:
Min: 0
Max: 3
b5-40
(17FH)
Frequency Reference Monitor
Content During PI
0: Frequency Reference (U1-01) After PI
1: Frequency Reference (U1-01)
Default: 0
Min: 0
Max: 1
b5-41
(160H)
PI Unit Selection
0: WC (Inch of Water)
1: PSI (ib/Sq inch)
2: GPM (Gallons/min)
3: F (Deg Fahrenheit)
4: CFM (Cubic ft/min)
5: CMH (Cubic M/h)
6: LPH (Liters/h)
7: LPS (Liters/s)
8: Bar (Bar)
9: Pa (Pascals)
10: C (Deg Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPN (Liters/min)
14: CMM (Cubic M/min)
Default: 0
Min: 0
Max: 14
b5-42
(161H)
PI Output Monitor Calculation
Method
0: Linear unit
1: Square root unit
2: Quadratic unit
3: Cubic unit
Default: 0
Min: 0
Max: 3
b5-43
(162H)
Custom PI Output Monitor
Setting 1
U5-14, U5-15 show Custom PI output. U5-14 shows the upper 4digits and U5-15 shows the
lower 4 digits.
It shows 999999.99 maximum. b5-43 and b5-44 is used for setting maximum monitor value at
maximum frequency.
Default: 0
Min: 0
Max: 9999
b5-44
(163H)
Custom PI Output Monitor
Setting 2
Default: 0.00
Min: 0.00
Max: 99.99
b5-45
(164H)
Custom PI Output Monitor
Setting 3
b5-07,-08 show Custom PI output.b5-45 is used for setting the minimum display value at o
speed. This function can be effective when b5-42 is set to 1 (Linear unit)
Default: 0.0
Min: 0.0
Max: 999.9
b5-46
(165H)
PI Setpoint Monitor Unit Selection
0: WC (Inch of Water)
1: PSI (ib/Sq inch)
2: GPM (Gallons/min)
3: F (Deg Fahrenheit)
4: CFM (Cubic ft/min)
5: CMH (Cubic M/h)
6: LPH (Liters/h)
7: LPS (Liters/s)
8: Bar (Bar)
9: Pa (Pascals)
10: C (Deg Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPN (Liters/min)
14: CMM (Cubic M/min)
Default: 0
Min: 0
Max: 14
b5-47
(17DH)
Reverse Operation Selection 2 by
PI Output
Reverse operation selection when b5-01 = 3 or 4.
0: Zero limit when PI output is a negative value.
1:Reverse operation when PI output is a negative value
(Zero limit if the reverse operation is prohibited by b1-04).
Default: 1
Min: 0
Max: 1
<5> Default setting is dependent on PI setpoint scaling (b5-20).
No.(Addr.)
Name
Description
Setting
Page
b8-01
(1CCH)
Energy Saving Control Selection
0: Disabled
1: Enabled
Default:
Min: 0
Max: 1
b8-04
(1CFH)
Energy Saving Coefficient Value
Determines the level of maximum motor efficiency. Setting range is 0.0 to 2000.0 maximum
output up to 3.7 kW. Refer to
Model Number and Nameplate Check on page 29
.
Default:
Min: 0.00
Max: 655.00
b8-05
(1D0H)
Power Detection Filter Time
Sets a time constant filter for output power detection.
Default: 20 ms
Min: 0 ms
Max: 2000 ms
No.(Addr.)
Name
Description
Setting
Page
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
OLV/PM
V/f
common_
TMonly
OLV/PM
V/f
common_
TMonly
OLV/PM
V/f
common_
TMonly
SIEP_C710616_35.book 365 ページ 2015年11月30日 月曜日 午後2時2分