4 Electrical Installation
YASKAWA ELECTRIC
TOBP C730600 39A YASKAWA AC Drive-Option Card DI-A3 Installation Manual
15
◆
Terminal Functions
Table 2 Terminal Function Selection
Termin
al
Block
Termin
al
BCD, Signed
BCD,
Unsigned
Binary, Signed
F3-01 = 0 to 5
F3-01 = 6
<1>
F3-01 = 7
8 bit
12 bit
16 bit
16 bit
8 bit
12 bit 16 bit
F3-03 = 0
F3-03 = 1
F3-03 = 2
F3-03
= 0
F3-03
= 1
F3-03
= 2
TB2
D0
<1> The setting F3-01 = 6 is enabled only when F3-03 = 2. Once enabled, the frequency reference can be set from 0.00
to 399.8 Hz with a BCD signal. Because the signed bit SI is also used, a negative reference cannot be input. The
smallest bit of the first digit starts with 2, so that 0.02 Hz is the smallest unit that can be used for the frequency
reference setting.
1 digit
(0 to 9)
1
1 digit
(0 to 9)
1
1 digits
(0 to 9)
1
1 digit
(0 to 9)
2
bit 0
bit 0
bit 0
D1
2
2
2
4
bit 1
bit 1
bit 1
D2
4
4
4
8
bit 2
bit 2
bit 2
D3
8
8
8
2 digits
(0 to 9)
1
bit 3
bit 3
bit 3
D4
2 digits
(0 to
15)
1
2 digits
(0 to
15)
1
2 digits
(0 to 9)
1
2
bit 4
bit 4
bit 4
D5
2
2
2
4
bit 5
bit 5
bit 5
D6
4
4
4
8
bit 6
bit 6
bit 6
D7
8
8
8
3 digits
(0 to 9)
1
bit 7
bit 7
bit 7
TB3
D8
–
–
3 digits
(0 to
15)
1
3 digits
(0 to 9)
1
2
–
bit 8
bit 8
D9
–
2
2
4
–
bit 9
bit 9
DA
–
4
4
8
–
bit 10
bit 10
DB
–
8
8
4 digits
(0 to 9)
1
–
bit 11
bit 11
DC
–
–
–
–
4 digits
(0 to
15)
1
2
–
–
bit 12
DD
–
–
2
4
–
–
bit 13
DE
–
–
4
8
–
–
bit 14
DF
–
–
8
5 digits
(0 to 3)
1
–
–
bit 15
TB1
SI
Signed
0: Forward 1: Reverse
2
Signed
0: Forward 1: Reverse
SE
Set (Read) signal
1: Reads values set to D0 to DF, SI
SP
24 V
±
5% internal power supply
SC
Input signal common
SN
Internal power supply common: 0 V
SD
Cable shield 2 (open)
FE
Shield ground