YASKAWA
TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide
91
Three-Phase 400 V Class
Table 15.7 Recommended Fuse (Three-Phase 400 V Class)
Drive Model
Fuse
Manufacturer: Bussmann
Model
Qty
4002
FWH-50B
3
4003
FWH-50B
2
4005
FWH-50B
2
4006
FWH-60B
2
4007
FWH-60B
2
4009
FWH-60B
2
4015
FWH-80B
2
4018
FWH-90B
2
4024
FWH-150B
2
4031
FWH-200B
2
4039
FWH-200B
2
4045
FWH-225A
2
4060
FWH-250A
2
4075
FWH-275A
2
4091
FWH-275A
2
4112
FWH-300A
FWH-325A
2
4150
FWH-400A
FWH-450A
2
4180
FWH-500A
FWH-600A
2
4216
FWH-600A
FWH-700A
2
4260
FWH-700A
FWH-800A
2
4304
FWH-800A
FWH-1000B
2
4371
FWH-1000B
FWH-1200B
2
4414
FWH-1200B
FWH-1400A
2
4453
FWH-1200B
FWH-1600A
2
4605
FWH-1600A
2
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
◆
EMC Directive
Drives with built-in EMC filters (models 2xxxB, 4xxxB) were tested in accordance with European standard IEC/
EN 61800-3:2004/A1:2012, and comply with the EMC Directive.
Use drives with built-in EMC filters or install external EMC filters to the drive input side to comply with the
EMC Directive. Refer to
Installing the External EMC Noise Filter on page 98
for the installation of the EMC
filter.
■
Install a Drive to Conform to the EMC Directive
Install drive models 2xxxB and 4xxxB with this procedure to comply with the EMC Directive when the drive is a
single unit or installed in a larger device.
1.
Install the drive on a grounded metal plate.
EN