YASKAWA CM093 Manual Download Page 6

Yaskawa Electric America, Inc. – 

www.yaskawa.com

IG.V7.26, Page 6 of 11

Date: 05/24/2010 Rev: 10-05

V7 EtherNet/IP Option Kit

CM093

23. Notes: 

a.

It is strongly recommended that shielded CAT-5 cable be used.

Verify that the shield is continuous to the drive and that it is grounded
only at the drive end.

b. Switches implementing IGMP snooping are strongly recommended.

When IGMP snooping is used, devices will only receive the multicast
packets in which they are interested.

c. To simplify the drive configuration, EDS file can be obtained at

www.yaskawa.com

. Select 

Downloads, By Inverter Drives, By

Product,

 and 

Network Comms-Ethernet

. Then select the appropriate

EDS file based on the drive series and the latest version from those listed.
EDS files for individual drive models are compressed into a single Zip

file and need to be unzipped to a temporary directory in order to be
installed.

d. The maximum number of connections is 1 for I/O, 4 for Explicit, 2 for

DriveWizard.

e.

DriveWizard version 6.1 or later with a custom database is required

for DriveWizard to operate with this option. Install DriveWizard with the
“Custom” install option checked and the appropriate databases selected.

24.

V7 EtherNet/IP Option Kit

 fault codes

The table of EtherNet/IP fault codes returned by the drive is shown below.
See Yaskawa Standard Speed/Torque Output Instance 155 (9Bh) later in the
manual for details on where these fault codes can be used. Refer to the V7
manual (TM.V7.01) for drive specific information on the fault returned.

EtherNet/IP

 Fault Code

[hex]

Description

EtherNet/IP

 Fault Code

[hex]

Description

0000h

None

5300h

Operator Disconnected (OPA)

2200h

Inverter Overload (OL2)

5300h

Fxx Errors (01,02,03,05,09,10,11)

2220h

Motor Overload (OL1)

7500h

EtherNet/IP

 Communication Error (BUS)

2221h

Overtorque Detection 1 (OL3)

8321h

Undertorque Detection 1 (UL3)

2300h

Overcurrent (OC)

9000h

External Fault on Terminal S3 (EF3)

3210h

DC Bus Overvoltage (OV)

9000h

External Fault on Terminal S4 (EF4)

3220h

DC Bus Undervoltage (UV1)

9000h

External Fault on Terminal S5 (EF5)

4200h

Heatsink Over-temperature (OH)

9000h

External Fault on Terminal S6 (EF6)

4210h

Heatsink Maximum Temperature (OH1)

9000h

External Fault on Terminal S7 (EF7)

4300h

Motor Overheat 1 (OH3)

9000h

External Fault Through Option Card (EF0)

5110h

Control Power Undervoltage (UV2)

Summary of Contents for CM093

Page 1: ...e the operator keypad 7 Remove the CN2 cover from the V7 terminal housing Carefully snip the 3 tabs connecting the CN2 cover on the V7 housing and remove the cover 8 Attach the Mounting Bracket Align the mounting bracket as shown in the figure to the right Secure the mounting bracket to the V7 drive s housing using the M3 x 8 screw 9 Wire the V7 drive I O terminals prior to mounting the V7 EtherNe...

Page 2: ...e Intermark RFC 13 and connect the ferrite as close to the RJ 45 connection as possible Secure the ferrite to the Ethernet cable with the provided cable tie If the ferrite cannot be mounted in your installation please contact Yaskawa for application assistance See the figure in the lower right corner of this page c Attach the provided ferrites to the V7 drive motor and power leads as close to the ...

Page 3: ...nnection and select Properties from the drop down menu c Select Internet Protocol TCP IP from the components displayed Note If a TCP IP selection is not available it may be installed by selecting Install Administrator access to the PC and the OS operating system installation CD ROMs may also be required 1 Select Properties Note If the PC is on a building or office network disconnect it from that n...

Page 4: ...y be limited or nonfunctional if the gateway usage setting and gateway address do not match the network infrastructure in which it is installed 1 Do not use default gateway in system Select this radio button to disable the gateway when there is no external gateway in the system 2 Use default gateway in system Select this radio button to enable the gateway when there is an external gateway in the s...

Page 5: ... wait approximately 10 seconds for the power up cycle to complete Note Additional wait time approximately two minutes may be required if utilizing the DHCP feature of this card and the DHCP server is not available or it did not respond to the request for an IP address The V7 EtherNet IP Option Kit will indicate that the load defaults process is complete when the MS RUN LED is displaying a steady G...

Page 6: ... to operate with this option Install DriveWizard with the Custom install option checked and the appropriate databases selected 24 V7 EtherNet IP Option Kit fault codes The table of EtherNet IP fault codes returned by the drive is shown below See Yaskawa Standard Speed Torque Output Instance 155 9Bh later in the manual for details on where these fault codes can be used Refer to the V7 manual TM V7 ...

Page 7: ...utput Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Instance 0h Network Speed Reference Network Run Command Fault Reset Run Reverse Run Forward 21 15h 1h 2h Speed Reference Low Byte Scaled by parameter n152 3h Speed Reference High Byte Scaled by parameter n152 Output Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Instance 0h Fault Reset Run Forward 22 16h 1h 2h Speed Reference Low Byt...

Page 8: ...lt 70 46h 1h Reserved 2h Output Frequency Low Byte Scaled by parameter n152 U 02 3h Output Frequency High Byte Scaled by parameter n152 U 02 Input Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Instance 0h Speed Agree Net Reference Net Run Stop Drive Ready Running Reverse Running Forward Alarm Fault 71 47h 1h Reserved 2h Output Frequency Low Byte Scaled by parameter n152 U 02 3h Output Frequ...

Page 9: ...Output Frequency Low Byte Scaled by parameter n152 U 02 3h Output Frequency High Byte Scaled by parameter n152 U 02 4h Motor Torque Low Byte 0 1 U 08 Available in OLV control mode only n002 1 5h Motor Torque High Byte 0 1 U 08 Available in OLV control mode only n002 1 6h 7h Reserved 8h Frequency Reference Low Byte Scaled by parameter n152 U 01 9h Frequency Reference High Byte Scaled by parameter n...

Page 10: ...ination of Motor Speed 5h GF Ground Fault 5h EF8 External Fault Terminal S8 F7U G7U Only 5h SVE Zero Servo Fault F7U G7U and G5M in Closed loop flux vector mode FVC only 6h OC Overcurrent Fault 6h FAN Drive Cooling Fan Fault models with internal cooling fans only 6h EF0 External Communications Fault 7h OV Overvoltage Fault 7h OS Overspeed Fault 7h Not Used 8h OH Heatsink Over temperature Fault 8h ...

Page 11: ...Note Using the Yaskawa AC Drive EtherNet IP Option with Controllogix Compactlogix Programmable Controllers AN AFD 09 Application Note Commissioning the Yaskawa Drive EtherNet IP Option with the Rockwell BOOTP DHCP Server AN AFD 10 EtherNet IP CONFORMANCE TESTED is a certification mark of ODVA YASKAWA ELECTRIC AMERICA INC Chicago Corporate Headquarters 2121 Norman Drive South Waukegan IL 60085 U S ...

Reviews: