Main and Control Circuit
Section 4
•
Signal leads and feedback leads (PG) must be separated from control leads main circuit leads, and any other
power cables, to prevent erroneous operation caused by electrical noise.
•
Lead length should NOT EXCEED 164 feet (50 meters). Wire sizes should be determined considering the voltage
drop.
•
All AC relays, contactors and solenoids should have RC surge supressors installed across their coils.
•
All DC relays, contactors and solenoids should have diodes installed across their coils.
TO DRIVE
SIGNAL
TERMINALS
TO SHIELD
SHEATH
TERMINAL
(TERM. )
WRAP BOTH ENDS
OF SHEATH WITH
INSULATING TAPE
CRIMP
CONNECTION
SHIELD SHEATH
OUTER JACKET
DO NOT
CONNECT
TO
EXTERNAL
CIRCUIT
Figure 1-1. Shielded Sheath Termination